S8VK-X
9
Module Status and Network Status Indicators
Communication Reset Function
This function temporarily resets the communication settings to their
factory default values. Use this function when the IP address
previously set is no longer known and communication is not possible.
Setting Method
(1) With the reset key pressed, turn on the power supply.
(2) Continue to hold the reset key for 10 seconds.
While pressed, an alarm indicator will flash in 0.5-second
intervals.
(For models with an indication monitor, the main display and
operation indicator will also repeatedly turn all indicators on and
off in 0.5-second intervals.)
(3) After 10 seconds have elapsed, the system shifts into the
communication reset state, and the communication setting values
temporarily reset to their factory default values.
In the communication reset state, the alarm indicator will flash in
1-second intervals. (For models with an indication monitor, the
main display and operation indicator will return to normal
operation.)
(4) In the communication reset state, reset the communication
settings from the host device.
(5) After setting, turn on the power supply once again, and confirm
that the set values have been changed.
Note: 1.
After confirming that the product output indicator has turned
off, turn on the power supply once again.
2.
The only way to exit the communication reset state is to
restart the power supply.
3.
If you do not change the communication settings during step
(4), settings will return to their prior values once the
communication reset is ended.
Switching Indications
All indicators of the indication monitor will be lit for 1 second when power is turned on. After that, each status can be displayed using the Indication
switching key.
Note:
For the factory setting, the output voltage will be displayed when the power supply is first turned ON. Thereafter, the status before shutting
down will be displayed.
Name
Color
Status
Operating status
Module status
Indicator (MS)
Green
Lit
Normal
Flashing
---
Red
Lit
RAM abnormality, EEPROM abnormality
Flashing
Voltage measurement abnormality, current measurement abnormality
---
Not lit
No power supply
Green/Red
Flashing
When power is turned ON
Network status
Indicator (NS)
Green
Lit
Connection established
Flashing
Connection not established
Red
Lit
Multiple IP addresses
Flashing
Connection timeout
BOOTP server connection abnormality
---
Not lit
No power supply
Green/Red
Flashing
When power is turned ON
Power turned ON
During startup
(All indicators lit for approx. 1 sec.)
Before power is turned ON
(No indicators lit)
Output voltage
(Measures and displays
the output voltage of
this product.)
Output current
(Measures and displays
the output current of
this product.)
Peak hold current
(Records and displays
the maximum output
current of this product.)
Years
until replacement
Percentage
until replacement
Total run time
When
abnormal
(Hot, E06)
V A Apk
Yrs % kh
888
. .
V
240
.
A
100
.
Apk
150
.
Yrs
30
.
kh
100
kh
hot
V A Apk
Yrs
%
kh
200
.
/RST
/RST
/RST
/RST
/RST
/RST
/RST