S8VK-X

27

Period and Terms of Warranty

Warranty Period

The Power Supply warranty is valid for a period of Five years from the date of shipment from the factory.

Terms of Warranty

The warranty is valid only for the following operating conditions.
1. Average ambient operating temperature of the Power Supply: 40°C max.
2. Average load rate of 80% max.
3. Mounting method: Standard mounting
Note: The maximum ratings must be within the derating curve.

If the Power Supply fails for reasons attributable to OMRON within the above warranty period, OMRON will repair or replace the faulty part of the 
Power Supply at the place of purchase or the place where the Power Supply delivered without charge.
This warranty does not cover the following types of failures.

Recommended Replacement Periods and Periodic Replacement for 
Preventive Maintenance

The recommended replacement period for preventive maintenance is greatly influenced by the application environment of the Power Supply. As 
a guideline, the recommended replacement period is 7 to 10 years.

*

S8VK-X is equipped with a replacement time calculation function, and the approximate number of years until replacement based on the ambient 
temperature and load rate can be checked via indicator (types with indication monitors only) or communication.
To prevent failures or accidents that can be caused by using a Power Supply beyond its service live, we recommend that you replace the Power 
Supply as early as possible within the recommended replacement period.
However, bear in mind that the recommended replacement period is for reference only and does not guarantee the life of the Power Supply.

Many electronic components are used in the Power Supply and the Power Supply depends on the correct operation of these components to 
achieve the original Power Supply functions and performance. However, the influence of the ambient temperature on aluminum electrolytic 
capacitors is large, and the service life is reduced by half for each 10°C rise in temperature (Arrhenius law). When the capacity reduction life of the 
electrolytic capacitor is reached, the Power Supply failures or accidents may occur. We therefore recommend that you replace the Power Supply 
periodically to minimize product failures or accidents in advance.

*

The recommended replacement period applies under the following conditions: rated input voltage, load rate of 50% max., ambient temperature 
of 40°C max., and the standard mounting method.
This product model is designed with a service life of 10 years minimum under the above conditions.

(1) Failures that result from handling or operation of the Power Supply under conditions or in environments that are not given in this document 

and not given in any other specifications exchanged between OMRON and the customer

(2) Failures that originate in causes other than the delivered product itself
(3) Failures caused by disassembly, modification, or repair of the Power Supply by anyone other than OMRON
(4) Failures caused by applications or uses for which the Power Supply was not originally intended.
(5) Failures caused by factors that could not be anticipated with the scientific or technical knowledge available when the Power Supply was 

shipped.

(6) Failures caused by other causes for which OMRON is not responsible, such as natural disasters and other acts of God.

This warranty is limited to the individual Power Supply that was delivered and does not cover any secondary, subsequent, or related damages.

Содержание S8VK-X

Страница 1: ...t function at 150 240 and 480 W Side by side mounting possible up to 55 C UL Class 2 conformance 90 W or less Complies with EN IEC 61558 2 16 Coated PCBs for better resistance to environment Model Num...

Страница 2: ...ed output voltage DC Rated output current Maximum boost current Model number 30 W 100 to 240 VAC allowable range 85 to 264 VAC 90 to 350 VDC 5 V 5 A 1 6 A S8VK X03005 EIP 60 W 12 V 4 5 A 2 5 4 A S8VK...

Страница 3: ...ervoltage Protection on page 8 for details Series operation Yes For up to two Power Supplies external diodes required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on...

Страница 4: ...to two Power Supplies external diodes are required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on page 22 for details Output indicator Yes LED Green Alarm indicato...

Страница 5: ...al diodes required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on page 22 for details Output indicator Yes LED Green Alarm indicator Yes LED Red Indication monitor...

Страница 6: ...e satisfied Voltage range Do not use an inverter output for the product Inverters with an output frequency of 50 60 Hz are available but the rise in the internal temperature of the product may result...

Страница 7: ...rement Yes Yes 0 1 A 5 ms Measurement accuracy 5 percentage of rated output current 1 digit Peak hold current measurement Yes Yes 0 1 A 5 ms Measurement accuracy 5 percentage of rated output current 1...

Страница 8: ...s been removed Communication Specifications Note 1 Internal parts may possibly deteriorate or be damaged if a short circuited or overcurrent state continues during operation 2 Internal parts may possi...

Страница 9: ...pply 3 If you do not change the communication settings during step 4 settings will return to their prior values once the communication reset is ended Switching Indications All indicators of the indica...

Страница 10: ...approximately 15 years after purchase even if the replacement time calculation for years and percentage do not appear 2 The replacement time is accelerated or decelerated according to operating condi...

Страница 11: ...e product s time powered on is measured as continuous run time and the continuous run time increases in 1 min steps with use Continuous run time will be reset when power is turned off Time Chart Note...

Страница 12: ...Inrush current protection circuit Smoothing circuit Rectifier smoothing circuit Overvoltage detection circuit Current detection circuit Overcurrent circuit 250 VAC 8 0 A HBC Photocoupler V2 V1 V1 V2...

Страница 13: ...e detection circuit Voltage detection circuit Photocoupler Overcurrent detection circuit S8VK X24024 EIP Harmonic current emissions Fuse N1 N2 HBC Smoothing circuit 8 0 A Rectifier smoothing circuit L...

Страница 14: ...W 240 W 480 W S8VK X09024A EIP S8VK X12024A EIP S8VK X24024A EIP S8VK X48024A EIP Without Indication Monitor 30 W 60 W 90 W 120 W 240 W 480 W S8VK X03005 EIP S8VK X06012 EIP S8VK X06024 EIP S8VK X090...

Страница 15: ...ut voltage adjuster V ADJ Use to adjust the output voltage 14 Main display white Displays measured values 15 Operation indicator white V Lights up when the output voltage is indicated A Lights up duri...

Страница 16: ...ont side by side mounting This Power Supply can be used at an altitude of 3 000 m Between 2 000 and 3 000 m derate the load according to the following derating curve Horizontal separation 15 mm or mor...

Страница 17: ...10 4 7 2 3 90 1 86 40 1 S8VK X03005 EIP 30 W S8VK X06012 EIP 60 W S8VK X06024 EIP 60 W The above diagram shows S8VK X06024 EIP 2 3 3 5 5 4 5 4 Sliding 10 max Rail stopper 78 55 90 1 15 4 7 90 1 86 55...

Страница 18: ...1 4 1 111 4 5 4 38 1 5 4 4 Rail stopper S8VK X24024 EIP 240 W The above diagram shows S8VK X24024A EIP 10 0 6 0 6 19 8 108 8 124 1 22 Sliding 8 max 5 2 2 3 117 121 4 1 111 4 5 4 60 1 0 9 7 5 4 Rail st...

Страница 19: ...dels S82Y VK10F 41 35 0 1 40 50 35 25 10 7 3 2 4 5 dia 0 1 t 1 0 35 64 t 2 0 80 60 0 1 55 0 1 13 3 4 5 dia 0 1 Left side mounting Right side mounting 25 0 1 140 0 1 150 38 5 4 t 2 0 4 4 5 dia 0 1 240...

Страница 20: ...nd surge Mounting Take adequate measures to ensure proper heat dissipation to increase the long term reliability of the Power Supply Be sure to allow convection in the atmosphere around devices when m...

Страница 21: ...ires in order to prevent smoking or ignition Recommended Wire Type Input crossover wiring can be used for the input side of this Power Supply Do not use crossover wiring for more than five Power Suppl...

Страница 22: ...by using two Power Supplies You can make positive negative outputs with any of the models If positive and negative outputs are used connect Power Supplies of the same model as in the following figure...

Страница 23: ...ply Make sure that the maximum load does not exceed the capacity of one Power Supply Use the S8VK R or connect external diodes For backup operation with 30 W 60 W 90 W or 120 W Power Supplies use the...

Страница 24: ...release hole 2 With the flat blade screwdriver still inserted into the release hole insert the wire into the terminal hole until it strikes the terminal block 3 Remove the flat blade screwdriver from...

Страница 25: ...n it with excessive force Do not place heavy objects on the cord This may cause a wire to be broken Separate the communication cable into a high voltage and high current power line to prevent inductio...

Страница 26: ...voltage such as a lightning inrush is applied to the input In case there is no output voltage please check the following points before contacting us Checking overload protected status Check whether t...

Страница 27: ...wer Supply Many electronic components are used in the Power Supply and the Power Supply depends on the correct operation of these components to achieve the original Power Supply functions and performa...

Страница 28: ...ears Warranty 1 1 Refer to Period and Terms of Warranty on page 36 for details Model Number Structure Model Number Legend Note Not all combinations are possible Refer to List of Model number in Orderi...

Страница 29: ...85 C with no condensation or icing Ambient operating humidity 95 Storage humidity 95 max Vibration resistance 10 to 55 Hz maximum 5 G 0 42 mm half amplitude for 2 h each in X Y and Z directions Shock...

Страница 30: ...erating curve by 0 8 to reduce the load Does not apply for face up mounting 0 20 40 60 80 100 120 40 30 20 10 0 10 20 30 40 50 60 70 80 90 Load ratio Operating temperature C Note If using at an altitu...

Страница 31: ...Name Model number Dimensions Appearance Front mounting bracket S82Y VS10F Side mounting bracket S82Y VS10S 1 2 90 1 86 3 5 5 4 Rail Stopper 78 55 4 7 Sliding 10 max 90 1 5 4 32 1 S8V NFS203 S8V NFS20...

Страница 32: ...lt from aluminum abrasion Mounting Rail Material Aluminum PFP 100N PFP 50N 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the PFP 50N Mounting Rail Mat...

Страница 33: ...oduct in locations subject to direct sunlight Do not use locations where liquids foreign matter or corrosive gases may enter the interior of the product Mounting Take adequate measures to ensure prope...

Страница 34: ...wires for one product When using crossover wiring select wiring materials suitable for the total current that will flow to terminals Stripping length DIN Rail Mounting To mount the Block on a DIN Rai...

Страница 35: ...he following figure Recommended Flat blade Screwdriver Use a flat blade screwdriver to connect and remove wires Use the following flat blade screwdriver The following table shows manufacturers and mod...

Страница 36: ...e following types of failures 1 Failures that result from handling or operation of the product under conditions or in environments that are not given in this document and not given in any other specif...

Страница 37: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 38: ...oofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 11...

Отзывы: