Peak Hold Current

The output current maximum value is stored as the peak hold current.
(5 ms average value)
Measurement is not performed for approximately 3 seconds 
immediately after the input power is turned ON.

Peak Hold Curmrent Reset

When the peak hold current is displayed, it can be reset by pressing 
the Reset key for 3 seconds or more.

Note:

For types without an indication monitor, it is not possible to 
reset the peak hold current via reset key operation.

Replacement Time Calculation Function

This Power Supply is equipped with electrolytic capacitors. The 
electrolyte inside the electrolytic capacitors penetrates the sealing 
rubber and evaporates as time passes after it is manufactured. This 
causes deterioration of characteristics, such as decreasing the 
capacitance. Due to this deterioration of the characteristics of the 
electrolytic capacitor, this Power Supply decreases its performance 
as time passes. The replacement time calculation function calculates 
an approximate period left for maintenance of this Power Supply due 
to deterioration of electrolytic capacitors. Use this function to know the 
approximate replacement time of the Power Supply.

Note:

The replacement time calculation function indicates an 
approximate period left for maintenance, based on 
deterioration of the electrolytic capacitors. It does not predict 
failures resulting from other causes.

Principle of Operation

The deterioration speed of the electrolytic capacitors varies 
considerably with the ambient temperature. (Generally the speed 
follows the Arrhenius Law, i.e., for every 10°C increase in the 
temperature, the rate of degradation doubles.) The S8VK-X monitors 
the temperature inside the Power Supply, and calculates the amount 
of deterioration according to the running hours and internal 
temperature.

Note: 1.

Due to degradation of internal electronic parts, replace the 
Power Supply approximately 15 years after purchase even 
if the replacement time calculation for years and percentage 
do not appear.

2.

The replacement time is accelerated or decelerated 
according to operating conditions. Periodically check 
indication.

3.

The accuracy of the replacement time calculation function 
will be reduced in applications where the input power turns 
ON and OFF frequently.

Years until replacement

(Indication monitor)

 is indicated at the time of purchase (when initially powered on), 

and continues to be indicated for approximately one month. 
Afterward, the state of deterioration for the electrolytic capacitor is 
calculated based on the usage environment, and 

 is indicated 

when deterioration progresses. When the years until replacement 
reaches 5 years or less, it is indicated in 0.1 step increments within 
the range of 4.9 to 0.0. (Depending on the usage environment, the 
number of years may be indicated after 

 without 

 being 

indicated.)
(Communication)
Communication is calculated in 0.1 step increments within a range of 
15.0 to 0.0.

Note:

The number of years until replacement may vary if there are 
frequent load variations or in locations where the ambient 
temperature fluctuates drastically.

Percentage until replacement

With the number of years until replacement at the time of manufacture 
set as 100%, as deterioration of the electrolytic capacitor progresses 
through use, it decreases in 0.1% step increments.

Peak hold current reset

Peak hold current

Press      /RST for 3 seconds or more

Apk

00

.

Apk

150

.

Release      /RST

Power

rating during
manufacture

Power

rating during

replacement

Indication 

monitor

Indication 

monitor

Communication

ful

hlf

4.9

0.0

Percentage

indication

Year indication

Electrolytic capacitor

power rating

0.0

100

99.9

………

Communication

0.0

15.0

14.9

………

Relationship between electrolytic capacitor power rating and indicator

0%

30%

100%

Slope and replacement time 
vary according to temperature

Relationship between number of years and percentage until replacement

Years until replacement

P

ercentage until replacement

Manufacture

15 years

Now

4.5 years

Replacement

0 years

Содержание S8VK-X

Страница 1: ...t function at 150 240 and 480 W Side by side mounting possible up to 55 C UL Class 2 conformance 90 W or less Complies with EN IEC 61558 2 16 Coated PCBs for better resistance to environment Model Num...

Страница 2: ...ed output voltage DC Rated output current Maximum boost current Model number 30 W 100 to 240 VAC allowable range 85 to 264 VAC 90 to 350 VDC 5 V 5 A 1 6 A S8VK X03005 EIP 60 W 12 V 4 5 A 2 5 4 A S8VK...

Страница 3: ...ervoltage Protection on page 8 for details Series operation Yes For up to two Power Supplies external diodes required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on...

Страница 4: ...to two Power Supplies external diodes are required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on page 22 for details Output indicator Yes LED Green Alarm indicato...

Страница 5: ...al diodes required Parallel operation Yes For up to two Power Supplies Refer to Parallel Operation on page 22 for details Output indicator Yes LED Green Alarm indicator Yes LED Red Indication monitor...

Страница 6: ...e satisfied Voltage range Do not use an inverter output for the product Inverters with an output frequency of 50 60 Hz are available but the rise in the internal temperature of the product may result...

Страница 7: ...rement Yes Yes 0 1 A 5 ms Measurement accuracy 5 percentage of rated output current 1 digit Peak hold current measurement Yes Yes 0 1 A 5 ms Measurement accuracy 5 percentage of rated output current 1...

Страница 8: ...s been removed Communication Specifications Note 1 Internal parts may possibly deteriorate or be damaged if a short circuited or overcurrent state continues during operation 2 Internal parts may possi...

Страница 9: ...pply 3 If you do not change the communication settings during step 4 settings will return to their prior values once the communication reset is ended Switching Indications All indicators of the indica...

Страница 10: ...approximately 15 years after purchase even if the replacement time calculation for years and percentage do not appear 2 The replacement time is accelerated or decelerated according to operating condi...

Страница 11: ...e product s time powered on is measured as continuous run time and the continuous run time increases in 1 min steps with use Continuous run time will be reset when power is turned off Time Chart Note...

Страница 12: ...Inrush current protection circuit Smoothing circuit Rectifier smoothing circuit Overvoltage detection circuit Current detection circuit Overcurrent circuit 250 VAC 8 0 A HBC Photocoupler V2 V1 V1 V2...

Страница 13: ...e detection circuit Voltage detection circuit Photocoupler Overcurrent detection circuit S8VK X24024 EIP Harmonic current emissions Fuse N1 N2 HBC Smoothing circuit 8 0 A Rectifier smoothing circuit L...

Страница 14: ...W 240 W 480 W S8VK X09024A EIP S8VK X12024A EIP S8VK X24024A EIP S8VK X48024A EIP Without Indication Monitor 30 W 60 W 90 W 120 W 240 W 480 W S8VK X03005 EIP S8VK X06012 EIP S8VK X06024 EIP S8VK X090...

Страница 15: ...ut voltage adjuster V ADJ Use to adjust the output voltage 14 Main display white Displays measured values 15 Operation indicator white V Lights up when the output voltage is indicated A Lights up duri...

Страница 16: ...ont side by side mounting This Power Supply can be used at an altitude of 3 000 m Between 2 000 and 3 000 m derate the load according to the following derating curve Horizontal separation 15 mm or mor...

Страница 17: ...10 4 7 2 3 90 1 86 40 1 S8VK X03005 EIP 30 W S8VK X06012 EIP 60 W S8VK X06024 EIP 60 W The above diagram shows S8VK X06024 EIP 2 3 3 5 5 4 5 4 Sliding 10 max Rail stopper 78 55 90 1 15 4 7 90 1 86 55...

Страница 18: ...1 4 1 111 4 5 4 38 1 5 4 4 Rail stopper S8VK X24024 EIP 240 W The above diagram shows S8VK X24024A EIP 10 0 6 0 6 19 8 108 8 124 1 22 Sliding 8 max 5 2 2 3 117 121 4 1 111 4 5 4 60 1 0 9 7 5 4 Rail st...

Страница 19: ...dels S82Y VK10F 41 35 0 1 40 50 35 25 10 7 3 2 4 5 dia 0 1 t 1 0 35 64 t 2 0 80 60 0 1 55 0 1 13 3 4 5 dia 0 1 Left side mounting Right side mounting 25 0 1 140 0 1 150 38 5 4 t 2 0 4 4 5 dia 0 1 240...

Страница 20: ...nd surge Mounting Take adequate measures to ensure proper heat dissipation to increase the long term reliability of the Power Supply Be sure to allow convection in the atmosphere around devices when m...

Страница 21: ...ires in order to prevent smoking or ignition Recommended Wire Type Input crossover wiring can be used for the input side of this Power Supply Do not use crossover wiring for more than five Power Suppl...

Страница 22: ...by using two Power Supplies You can make positive negative outputs with any of the models If positive and negative outputs are used connect Power Supplies of the same model as in the following figure...

Страница 23: ...ply Make sure that the maximum load does not exceed the capacity of one Power Supply Use the S8VK R or connect external diodes For backup operation with 30 W 60 W 90 W or 120 W Power Supplies use the...

Страница 24: ...release hole 2 With the flat blade screwdriver still inserted into the release hole insert the wire into the terminal hole until it strikes the terminal block 3 Remove the flat blade screwdriver from...

Страница 25: ...n it with excessive force Do not place heavy objects on the cord This may cause a wire to be broken Separate the communication cable into a high voltage and high current power line to prevent inductio...

Страница 26: ...voltage such as a lightning inrush is applied to the input In case there is no output voltage please check the following points before contacting us Checking overload protected status Check whether t...

Страница 27: ...wer Supply Many electronic components are used in the Power Supply and the Power Supply depends on the correct operation of these components to achieve the original Power Supply functions and performa...

Страница 28: ...ears Warranty 1 1 Refer to Period and Terms of Warranty on page 36 for details Model Number Structure Model Number Legend Note Not all combinations are possible Refer to List of Model number in Orderi...

Страница 29: ...85 C with no condensation or icing Ambient operating humidity 95 Storage humidity 95 max Vibration resistance 10 to 55 Hz maximum 5 G 0 42 mm half amplitude for 2 h each in X Y and Z directions Shock...

Страница 30: ...erating curve by 0 8 to reduce the load Does not apply for face up mounting 0 20 40 60 80 100 120 40 30 20 10 0 10 20 30 40 50 60 70 80 90 Load ratio Operating temperature C Note If using at an altitu...

Страница 31: ...Name Model number Dimensions Appearance Front mounting bracket S82Y VS10F Side mounting bracket S82Y VS10S 1 2 90 1 86 3 5 5 4 Rail Stopper 78 55 4 7 Sliding 10 max 90 1 5 4 32 1 S8V NFS203 S8V NFS20...

Страница 32: ...lt from aluminum abrasion Mounting Rail Material Aluminum PFP 100N PFP 50N 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the PFP 50N Mounting Rail Mat...

Страница 33: ...oduct in locations subject to direct sunlight Do not use locations where liquids foreign matter or corrosive gases may enter the interior of the product Mounting Take adequate measures to ensure prope...

Страница 34: ...wires for one product When using crossover wiring select wiring materials suitable for the total current that will flow to terminals Stripping length DIN Rail Mounting To mount the Block on a DIN Rai...

Страница 35: ...he following figure Recommended Flat blade Screwdriver Use a flat blade screwdriver to connect and remove wires Use the following flat blade screwdriver The following table shows manufacturers and mod...

Страница 36: ...e following types of failures 1 Failures that result from handling or operation of the product under conditions or in environments that are not given in this document and not given in any other specif...

Страница 37: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 38: ...oofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 11...

Отзывы: