4 - 5
4 Operations
S8BA-series Uninterruptible Power Supply (UPS) User’s Manual (U726)
4
4
-1-2
B
a
ckup oper
atio
n time setting / Batter
y r
eplaceme
nt mode selection switch
Sets the backup operation time.
For the setting, use a 2.5 mm or less flat-head screwdriver.
4-1-2
Backup operation time setting / Battery replacement mode selec-
tion switch
Switching to the backup operation time setting / Battery
replacement mode
Set value
Description
SV FREE
Maximum (back up until battery runs out)
0.5
30 seconds
1
1 min.
2
2 min.
3
3 min.
5
5 min.
10
10 min.
15
15 min.
20
20 min.
BATT REP
Switches to the battery replacement mode.
Set at the time of replacing the battery unit.