5 Maintenance and inspection
5 - 6
S8BA-series Uninterruptible Power Supply (UPS) User’s Manual (U726)
For details on the precautions to be taken when replacing the battery unit, refer to
on page 15 in the "Safety precautions" at the beginning of this manual.
Precautions for Safe Use
Be sure to activate the battery replacement mode before replacing the battery unit.
• When replacing the battery unit, set the unit to "BATT REP" (Battery unit replacement mode)
using the mode selection / backup operation time selection switch.
• The battery life counter is automatically reset when the battery unit is replaced.
If the battery unit is replaced without setting the battery replacement mode, the battery life
may not be detected accurately because the battery life counter is not reset.
Additional Information
Buy a new battery unit for replacement.
1
Set the unit's mode selection / backup operation time selection switch to the battery replace-
ment mode.
The setting is complete when the LED indicators show "[DC ON] LED: Green (Blink 0) / [BATT]
LED: Yellow (Blink 0) / [ALERT] LED: Red (Blink 0)" for a few seconds before showing "[DC ON]
LED: Green (Blink 4) / [BATT] LED: Yellow (Blink 4) / [ALERT] LED: Red (Blink 4)".
5-2-2
Procedure for replacing the battery unit
Set to “BATT REP”.
Содержание S8BA-24D24D480SBF
Страница 5: ...Manual Structure 4 S8BA Series Uninterruptible Power Supply UPS User s Manual U726 ...
Страница 21: ...Revision History 20 S8BA series Uninterruptible Power Supply UPS User s Manual U726 ...
Страница 27: ...1 Overview of the product 1 6 S8BA series Uninterruptible Power Supply UPS User s Manual U726 ...
Страница 45: ...3 Installation and connection 3 12 S8BA series Uninterruptible Power Supply UPS User s Manual U726 ...
Страница 55: ...4 Operations 4 10 S8BA series Uninterruptible Power Supply UPS User s Manual U726 ...
Страница 65: ...5 Maintenance and inspection 5 10 S8BA series Uninterruptible Power Supply UPS User s Manual U726 ...