19
S82H-3
S82H-3
Specifications
■
Ratings/Characteristics
Note:
1.
A surge absorber is provided for the input circuit. To test the dielectric strength and insulation resistance of the power supply,
remove the short bar attached across the FG and ACG terminals.
2.
Defined with a 100% load and the rated input voltage (100 or 200 VAC).
Item
15 W
30 W
50 W
Efficiency (typical)
65% min.
70% min.
Input
Voltage
100 V (85 to 132 VAC)/200 V (170 to 264 VAC) selectable
Frequency
47 to 450 Hz
Current
(see note 2)
100-VAC input
0.5 A max.
0.9 A max.
1.3 A max.
200-VAC input
0.3 A max.
0.6 A max.
0.8 A max.
Leakage current
(see note 2)
100-VAC input
0.5 mA max.
200-VAC input
1 mA max.
Inrush current
(see note 2)
100-VAC input
25 A max.
200-VAC input
50 A max.
Noise filter
Yes
Output
Voltage adjustment range
±
10% (adjustable with variable resistor (V.ADJ))
Ripple (see note 2)
2% (p-p) max.
Input variation influence
0.5% max. (at 85 to 132 VAC/170 to 264 VAC input, 100% load)
Load variation influence
2% max. (with rated input, 10 to 100% load)
Temperature variation influence
0.05%/
°
C max. (with rated I/O at an ambient temperature range between 0
°
C to
40
°
C)
Startup time
200 ms max. (up to 90% of output voltage at rated input and output)
Hold time (see note 2)
20 ms min. (up to 90% of output voltage at rated input and output)
Additional
function
Overload protection
105% min. of rated load current (typical), inverted L drop type, automatic reset
Overvoltage protection
No
Remote sensing
No
Remote control
No
Other
Ambient temperature
Operating: See the derating curve in the
“Engineering Data”
section
Storage:
–20
°
C to 85
°
C
Ambient humidity
Operating: 30% to 90%
Storage:
20% to 95%
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between all inputs and all outputs/GR terminal) (see
note 1)
500 VDC, 50/60 Hz for 1 min (between all outputs and all inputs/GR terminal)
Insulation resistance
100 M
Ω
min. at 500 VDC (between all outputs and all inputs/GR terminal)
Vibration resistance
Malfunction: 10 to 55 Hz, 0.375-mm single amplitude for 2 hrs each in X, Y, and
Z directions
Shock resistance
Malfunction: 294 m/s
2
(approx. 30G), 3 times each in
±
X,
±
Y, and
±
Z directions
Output indicator
Yes (red)
Common mode noise
4 V p-p max.
Electromagnetic interference (see
note 2)
Conforms to FCC class B
Approved standards
UL1012, CSA E.B.1402C
Weight
400 g max.
520 g max.
660 g max.