17
S82H
S82H
Fan Replacement
The fan must be replaced when a fan alarm is output. Contact
your OMRON representative for details about fan replacement.
When replacing the fan, unscrew the case fixing screws (A) to
remove the rear plate and then unscrew the fan fixing screws (B)
to remove the fan.
Note:
The 600-W models incorporate two fans.
Terminal Expansion Bracket
The maximum current density should be 20 A per one M4 termi-
nal screw.
A terminal expansion bracket is available for use with the 600-W
Power Supply when several loads need to be connected.
Wiring Precautions
The Power Supply is provided with reinforced insulation between
the primary and secondary terminals. When using the secondary
circuit as an SELV circuit, the circuit connected to the output ter-
minals and auxiliary function terminals must be an SELV circuit.
300 W
600 W
Fan
(A)
(A)
(B)
Fans
(A)
(B)
(A)
(A)
(B)
(B)
(B)
Brackets: 2
M4 x 8 terminal screws: 12
M5 x 12 terminal screws: 4
S82Y-D60T