Figure 5.24 Safe Disable Operation
■
Switching from Usual Operation to “Safe Torque Off”
Turn OFF (open) safety input terminal H1 or H2 to enable the Safe Disable function. When the Safe Disable
function is enabled while the motor is operating, the drive output and motor torque turn off and the motor always
coasts to stop. The
b1-03 [Stopping Method Selection]
setting does not have an effect on the stopping method.
The
“
Safe Torque Off
”
status is only possible with the Safe Disable function. Clear the Run command to stop the
drive. Turning off drive output (a baseblock condition) ≠
“
Safe Torque Off
”
.
Note:
•
When it is necessary to ramp to stop the motor, do not turn off terminals H1 and H2 until the motor fully stops. This will prevent the
motor from coasting to stop during usual operation.
•
A maximum of 3 ms will elapse from when terminals H1 or H2 shut off until the drive switches to the "Safe Torque Off" status. Set the
OFF status for terminals H1 and H2 to hold for at least 3 ms. The drive may not be able to switch to the
“
Safe Torque Off
”
status if
terminals H1 and H2 are only open for less than 3 ms.
■
Going from “Safe Torque Off” to Usual Operation
The safety input will only release when there is no Run command.
•
During Stop
When the Safe Disable function is triggered during stop, close the circuit between terminals H1-HC and H2-HC
to disable
“
Safe Torque Off
”
. Enter the Run command after the drive stops correctly.
•
During Run
When the Safe Disable function is triggered during run, close the circuit between terminals H1-HC and H2-HC
to disable
“
Safe Torque Off
”
after clearing the Run command. Enter the Stop command, then enter the Run
command when terminals H1 and H2 are ON or OFF.
◆
Safe Disable Monitor Output Function and Keypad Display
Table 5.23 Safe Disable Input and External Device Monitor (EDM) Terminal Status
Input Channel Status
Safety Monitor Output Status
Drive Output
Status
Keypad
Display
READY LED
Modbus Register
0020H
Input 1
(H1-HC)
Input 2
(H2-HC)
MFDO Terminal
(H2-xx = E)
MFDO Terminal
(H2-xx = 10E)
bit C
bit D
ON
(Close the circuit)
ON
(Close the circuit)
OFF
ON
Baseblock
(Drive ready)
Normally
displayed
READY:
Illuminated
0
0
OFF
(Open)
ON
(Close the circuit)
OFF
ON
Safety status
(STo)
SToF
(Flashing)
ALM/ERR:
Flashing
1
0
ON
(Close the circuit)
OFF
(Open)
OFF
ON
Safety status
(STo)
SToF
(Flashing)
ALM/ERR:
Flashing
1
0
OFF
(Open)
OFF
(Open)
ON
OFF
Safety status
(STo)
STo
(Flashing)
READY: Flashing
0
1
■
Safety Function Status Monitor
The drive Safety monitor output sends a feedback signal about the status of the Safety function. The Safety
monitor output is one of the possible settings available for the MFDO terminals. If there is damage to the Safe
Disable circuit, a controller (PLC or safety relay) must read this signal as an input signal to hold the
“
Safe Torque
Off
”
status. This will help verify the condition of the safety circuit. Refer to the manual for the safety device for
more information about the Safety function.
It is possible to switch polarity of the Safety monitor output signal with the MFDO function settings. Refer to
for setting instructions.
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...