58
6. Using the UPS monitoring software and contact signal
Connector
Connect the remote ON/OFF connector
included with the product.
6. Remote ON/OFF connector (female)
(1) Connect the connector:
FUPS Shutdown
Disconnect the connector: FUPS Start-up
(2) The corresponding warning
Remote ON (+)
Remote OFF (--)
10V
BL
TR
BU/NBU
BS
COM
2k
Ω
WB
Front view
Screw size: Inch screw
#4-40 U N C
Pin assignment
Pin number
Signal name
1
Remote ON/OFF (+)
2
Remote ON/OFF (--)
1 2
7. Contact Signal ratings
●
Signal output (BL, TR, BU/NBU, WB)
●
UPS Stop Signal input (BS)
Photo coupler ratings
Input voltage HIGH
5 to 15 VDC
Appliable voltage:
35 VDC or less
LOW
0.7 VDC or less
Maximum current:
10 mA
●
Remote ON/OFF
Voltage between terminals: 10 VDC
Current when closed:
max.10 mA
8. Contact Signal circuit inside the UPS