Power output stop delay time setting (setting switches 5 and 6 ) … Factory
setting: OFF and OFF
0 second
60 seconds
120 seconds
Setting switch 5 Setting switch 6
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Does not stop
power output
Power output stop
delay time
1 2
5
3 4
8
6 7
ON
DIP
●
Auto battery test ON/OFF setting (setting switch 3 ) … Factory setting: OFF
1 2
5
3 4
8
6 7
ON
DIP
OFF: The battery test is automatically executed once every 4 weeks.
ON: The auto battery test is disabled.
Use this setting to disable Battery Mode for for the regularly performed auto battery test.
1 2
5
3 4
8
6 7
ON
DIP
●
Auto restart setting (setting switch 2 ) … Factory setting: OFF
OFF: Automatically restarts when power is restored.
After a power failure occurs and the UPS is shut down using the shutdown software or contact
signal, the UPS automatically starts up and begins to output when the commercial power is
restored.
ON: Does not automatically restart when power is restored.
After the unit is shut down with the UPS monitoring software or contact signal, it does not start up
when commercial power is restored. Startup is performed manually by turning the power switch
OFF and back ON again.