Hardware Arrangement
The coils and contacts in electromagnetic contacts and relays in an external circuit are sources of
noise. Do not install them close to the Panel PC. Locate them at least 100 mm away from the Panel
PC.
Example of Arrangement in Panel
AC I/O
device
Terminal block
DC I/O
device
OMRON
product
Wire Layout for the Power Supply
Observe the following points when wiring the power supply system.
• Separate the Panel PC power supply from the I/O device power supply and install a noise filter near
the Panel PC power supply feed section.
• Use an isolating transformer to significantly reduce noise between the Panel PC and the ground. In-
stall the isolating transformer between the Panel PC power supply and the noise filter, and do not
ground the secondary coil of the transformer.
• Keep the wiring between the transformer and the Panel PC as short as possible, twist the wires well,
and keep the wiring separate from high-voltage and power lines.
Unit power supply for Omron product
I/O power supply for Omron product
Power Supply System Diagram
Power circuits
Power supply for general operations circuits
Outlet (for peripheral devices)
I/O power supply for Omron product
Noise
filter
5 Installation
5 - 19
NY-series Industrial Panel PC Hardware User's Manual (W557)
5-3 Mount
5
5-3-7 Electrical Environment
Содержание NY532-1*00-111*13**0
Страница 42: ...Sections in this Manual 40 NY series Industrial Panel PC Hardware User s Manual W557...
Страница 86: ...3 Hardware Overview 3 28 NY series Industrial Panel PC Hardware User s Manual W557...
Страница 160: ...5 Installation 5 48 NY series Industrial Panel PC Hardware User s Manual W557...
Страница 208: ...Appendices A 16 NY series Industrial Panel PC Hardware User s Manual W557...
Страница 209: ...I Index I 1 NY series Industrial Panel PC Hardware User s Manual W557 I...
Страница 212: ......
Страница 213: ......