High Temperatures
Use the following cooling methods as required, taking into account the ambient temperature and the
amount of heating inside the panel.
l
Natural Cooling
Natural cooling relies on natural ventilation through slits in the panel, rather than using cooling devi-
ces such as fans or coolers. When using this method, observe the following points.
• Do not install the Panel PC at the top of the panel, where hot air tends to stagnate.
• To provide ventilation space above and below the Panel PC, leave sufficient distance from other
devices, wiring ducts, etc.
• Do not mount the Panel PC in the wrong direction (e.g., vertically or upside down). Doing so may
cause abnormal heating in the Panel PC.
• Do not install the Panel PC directly above any heat-generating equipment, such as heaters or
transformers.
• Do not install the Panel PC in a location exposed to direct sunlight.
Natural Cooling
OMRON
product
OMRON
product
l
Forced Ventilation
Forced ventilation with a fan in the top of the control cabinet.
Air filter
Fan
Forced Ventilation Method
OMRON
product
OMRON
product
l
Forced Air Circulation
Forced circulation with a fan inside the closed control cabinet.
5 Installation
5 - 16
NY-series Industrial Panel PC Hardware User's Manual (W557)
Содержание NY532-1*00-111*13**0
Страница 42: ...Sections in this Manual 40 NY series Industrial Panel PC Hardware User s Manual W557...
Страница 86: ...3 Hardware Overview 3 28 NY series Industrial Panel PC Hardware User s Manual W557...
Страница 160: ...5 Installation 5 48 NY series Industrial Panel PC Hardware User s Manual W557...
Страница 208: ...Appendices A 16 NY series Industrial Panel PC Hardware User s Manual W557...
Страница 209: ...I Index I 1 NY series Industrial Panel PC Hardware User s Manual W557 I...
Страница 212: ......
Страница 213: ......