5 I/O Refreshing
5 - 30
NX-series Digital I/O Unit User’s Manual (W521)
The network configuration is as follows.
A Slave Terminal with the following configuration is connected at EtherCAT node address 1. The
device names that are given in the following table are used.
The task period of the primary periodic task is 1 ms.
The Unit operation settings of the Input Unit NX-ID3344 are as follows.
Network Configuration
Unit number
Model
Unit
Device name
0
NX-ECC201
EtherCAT Coupler Unit
E001
1
NX-ID3344
Digital Input Unit that supports input refreshing
with input changed time
N1
2
NX-OD2154
Digital Output Unit that supports output refreshing
with specified time stamp
N2
Task Settings
Unit Operation Settings
Item
Set
value
Meaning
Time Stamp (Trigger Setting) : Input
Bit 00 Trigger Setting
FALSE
Trigger to read the input changed time: Rising Edge
Time Stamp (mode Setting) : Input Bit
00 Mode Setting
FALSE
Operation mode to read the input changed time: Continuous
(Last changed time)
Содержание NX-IA3117
Страница 34: ...Sections in this Manual 32 NX series Digital I O Unit User s Manual W521...
Страница 52: ...1 Features and System Configuration 1 18 NX series Digital I O Unit User s Manual W521...
Страница 56: ...2 Specifications 2 4 NX series Digital I O Unit User s Manual W521...
Страница 152: ...5 I O Refreshing 5 36 NX series Digital I O Unit User s Manual W521...
Страница 204: ...8 Digital Mixed I O Units 8 8 NX series Digital I O Unit User s Manual W521...
Страница 224: ...9 Troubleshooting 9 20 NX series Digital I O Unit User s Manual W521...
Страница 230: ...10 Inspection and Maintenance 10 6 NX series Digital I O Unit User s Manual W521...
Страница 290: ...Appendices A 60 NX series Digital I O Unit User s Manual W521 Installation Height 100 71 Unit mm...
Страница 337: ...I 1 I NX series Digital I O Unit User s Manual W521 Index...
Страница 340: ...I 4 NX series Digital I O Unit User s Manual W521 Index...