10 Troubleshooting
10 - 12
NX-series Position Interface Units User’s Manual (W524)
Event name
Control Parameter Error in Master
Event code
10410000 hex
Meaning
An error occurred in the control parameters that are saved in the master.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details
NX Unit
Detection
timing
When power is
turned ON to
the NX Unit
Error
attributes
Level
Minor fault
Recovery
When the
fail-soft opera-
tion for the
Communica-
tions Coupler
Unit is set to
stop, restart the
NX Unit and
then reset all
errors in Con-
troller.
When the
fail-soft opera-
tion for the
Communica-
tions Coupler
Unit is set to
fail-soft, restart
the NX Unit and
then reset
errors in Com-
munications
Coupler Unit.
Log category
System
Effects
User program
Continues.
Operation
I/O refreshing for the NX Unit stops.
Sys-
tem-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
There is an error in the area of the
non-volatile memory in the Com-
munications Coupler Unit in which
the Unit operation settings for the
NX Unit are saved.
Download the Unit operation set-
tings of the NX Unit again and
restart the Communications Cou-
pler Unit.
If the error occurs again even after
you make the above correction,
replace the Communications Cou-
pler Unit.
Do not turn OFF the power supply
to the NX Unit or disconnect Sys-
mac Studio communications while
transfer of the Unit operation set-
tings for the NX Unit or execution
of the NX_SaveParam instruction
is in progress.
The power supply to the NX Unit
was turned OFF or Sysmac Studio
communications were discon-
nected while writing the Unit oper-
ation settings was in progress.
Attached
information
None
Precautions/
Remarks
None
Содержание NX-EC0112
Страница 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Страница 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Страница 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Страница 70: ...2 Specifications and Application Procedures 2 14 NX series Position Interface Units User s Manual W524...
Страница 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Страница 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Страница 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Страница 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Страница 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Страница 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Страница 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Страница 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...