A - 43
Appendices
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
A-
3 List
of
NX Object
s
A
A-
3-2 Analog Inpu
t Unit
s
*1. The default value and data range for Number of Entries are as follows.
*2. The default value and data range for Ch
Range Setting are as follows.
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range
Unit
Data
type
Acc
ess
I/O
allo-
cat-
ion
Data
attri-
bute
5003
---
Input Range Setting
---
---
---
---
---
---
---
00
Number of Entries
*1
*1
---
USINT
RO
Not
pos-
sible
---
01
Ch1 Range Setting
*2
*2
---
UINT
RW
Not
pos-
sible
Y
02
Ch2 Range Setting
---
UINT
RW
Not
pos-
sible
Y
03
Ch3 Range Setting
---
UINT
RW
Not
pos-
sible
Y
04
Ch4 Range Setting
---
UINT
RW
Not
pos-
sible
Y
05
Ch5 Range Setting
---
UINT
RW
Not
pos-
sible
Y
06
Ch6 Range Setting
---
UINT
RW
Not
pos-
sible
Y
07
Ch7 Range Setting
---
UINT
RW
Not
pos-
sible
Y
08
Ch8 Range Setting
---
UINT
RW
Not
pos-
sible
Y
NX Units
Default value
Data range
NX-AD2203/AD2204/AD2208/
AD2603/AD2604/AD2608
2
2
NX-AD3203/AD3204/AD3208/
AD3603/AD3604/AD3608
4
4
NX-AD4203/AD4204/AD4208/
AD4603/AD4604/AD4608
8
8
Other models
0
0
NX Units
Set
value
Meaning
Default value
Data range
NX-AD2203/AD2204/AD2208/
AD3203/AD3204/AD3208/
AD4203/AD4204/AD4208
0
4 to 20 mA
0
0
1
0 to 10 V
2
-10 to +10 V
3
0 to 5 V
4
1 to 5 V
5
0 to 20 mA
Содержание NX-AD series
Страница 116: ...5 I O Refreshing 5 20 NX series Analog I O Units User s Manual for Analog Input Units and Analog Output Units W522 ...
Страница 148: ...6 Analog Input Units 6 32 NX series Analog I O Units User s Manual for Analog Input Units and Analog Output Units W522 ...
Страница 285: ...I 1 I NX series Analog I O Units User s Manual for Analog Input Units and Analog Output Units W522 Index ...
Страница 288: ...I 4 NX series Analog I O Units User s Manual for Analog Input Units and Analog Output Units W522 Index ...
Страница 289: ......