Appendices
A - 12
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
Unit name
Analog Input Unit (current input type)
Model
NX-AD3203
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12 ter-
minals)
I/O refreshing method
Free-Run refreshing
Indicators
TS indicator
Input method
Single-ended input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250
Ω
Resolution
1/8000 (full scale)
Overall
accuracy
25
°
C
±0.2% (full scale)
0
to
55
°
C
±0.4% (full scale)
Conversion time
250
μ
s/point
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 M
Ω
min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max., IOG: 0.1 A/termi-
nal max.
NX Unit power con-
sumption
• Connected to a CPU Unit
1.25 W max.
• Connected to a Communications Cou-
pler Unit
0.90 W max.
Current consumption
from I/O power supply
No consumption
Weight
70 g max.
Circuit layout
Installation orienta-
tion and restrictions
Installation orientation:
• Connected to a CPU Unit
Possible in upright installation.
• Connected to a Communications Coupler Unit
Possible in 6 orientations.
Restrictions: No restrictions
Terminal connection
diagram
Input disconnection
detection
Supported
AG
AMP
IOV
IOG
to 4+
Terminal block
250 Ω
AG: Analog circuit internal GND
NX bus
connector
(left)
I/O power
I/O power supply
−
I/O power
I/O power supply
−
NX bus
connector
(right)
Input +
24 V (Sensor power )
0 V (Sensor power supply
− /
Input
−
)
Three-wire sensor
IOV
IOG
IOV
IOG
IOV
IOG
IOV
IOG
IOG
IOV
IOV
A1
B1
A8
B8
IOG
IOG
IOV
IOV
IOG
24 VDC
A1
B1
A8
B8
Additional I/O
Power Supply Unit
Current Input Unit
NX-AD3203
Содержание NX-AD series
Страница 116: ...5 I O Refreshing 5 20 NX series Analog I O Units User s Manual for Analog Input Units and Analog Output Units W522 ...
Страница 148: ...6 Analog Input Units 6 32 NX series Analog I O Units User s Manual for Analog Input Units and Analog Output Units W522 ...
Страница 285: ...I 1 I NX series Analog I O Units User s Manual for Analog Input Units and Analog Output Units W522 Index ...
Страница 288: ...I 4 NX series Analog I O Units User s Manual for Analog Input Units and Analog Output Units W522 Index ...
Страница 289: ......