6 Analog Input Units
6 - 26
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
z
Correctable Range
The correctable range is -5 to 5% of the input full scale.
The correctable range for each input range is as follows.
All Analog Input Units
This section describes how to configure settings with the Sysmac Studio.
You can perform the user calibration even if you are using Support Software other than the Sysmac
Studio.
For details on how to configure the user calibration settings with Support Software other than Sysmac
Studio, refer to the operation manual for the Support Software that you are using.
1
Right-click the NX Unit, then select
User Calibration
from the menu.
Input range
Correctable range
0%
100%
-10 to +10 V
-11 to -9.0 V
9.0 to 11 V
4 to 20 mA
3.2 to 4.8 mA
19.2 to 20.8 mA
Target NX Units
Setting Method
Содержание NX-AD series