4-1
Section
Connecting to the RS-232C Port at the Host
62
CPU Unit Allocation DM Area Settings
Setting is written from the Programming Device (a Programming Console or CX-
Programmer) directly into the allocated DM Area (PC Setup) of the CPU Unit.
After the setting is written, it becomes effective by turning the power ON, restart-
ing the Unit, restarting the communication port, or execution of the STUP
instruction.
The following table shows the words allocated in the DM Area and the settings.
Allocated DM word
Value
Settings
Port 1
Port 2
Value
Settings
DM32000
DM32010
8200
1:N NT Link mode
DM32001
DM32011
000A
Communications baud rate (high-speed)
DM32006
DM32016
000
j
j
= The largest model number of the
connected PT (0 – 7)
For example, when connecting PTs with model numbers 3, 4, 5, and 6 to port 1,
set DM 32000 to 8200 Hex, DM 32001 to 000A Hex, and DM 32006 to 0006 Hex.
Connecting to a CS/CJ-series Serial Communications Unit
A CS-series Rack-mounted Unit: CS1W-SCU21
CJ-series: CJ1W-SCU41 (Port 2 is an RS-232C port.)
Reference: Serial Communications Boards and Serial Communications Units with lot num-
ber 991220 (12/20/99) and later support the high-speed 1:N NT Link. Boards and
Units with earlier lot numbers cannot be used.
Setting the Front Switches
Set the unit number of the Serial Communications Unit by using the rotary switch
located on the front panel. Set each switch with a flat blade screwdriver so that
the values or symbols in the setting value window agree with the following.
Set the unit number to 0 through F so
that it will not duplicate the numbers
used in other Units.
SCU21
RUN
ERC
SD1
RD1
RDY
ERH
SD2
RD2
No.
FE
D
C
B
A
9
8
7
6
5
4
32
10
UNIT
CS1W-SCU21
CJ1W-SCU41
Set the unit number to 0 through F so
that it will not duplicate the numbers
used in other Units.
Allocation DM Area Settings for CPU Unit
Setting is written from the Programming Device (a Programming Console or CX-
Programmer) directly into the allocated DM Area (PC Setup) of the CPU Unit.
After the setting is written, it becomes effective by turning the power ON, restart-
ing the Unit, restarting the communication port, or execution of the STUP
instruction.