6-2
Section
Responding to Displayed Error Messages
420
The remedies to take in accordance with the displayed cause are indicated in the
table below.
Error Details
Displayed Probable Cause
Remedy
Parity Error
Framing Error
Over-run Error
Communication parameters/
conditions set incorrectly.
Check if the settings at the host for parity bit, frame
length, communications speed, stop bit length and
flow control agree with those at the PT.
Over-run Error
The connecting cables are not
connected correctly.
Check the communication cable connection and
perform a conductivity test. If there is a fault,
replace the cable. For details on communication
cables, refer to
Connecting to the Host from the
RS-232C Port in section 4 or Connecting to the
Host from the RS-422A/485 Port in section 5 in the
Setup Manual.
Noise caused data corruption during
communication.
Carry out grounding work in accordance with the
conditions. (Refer to
Grounding in section 3 in the
Setup Manual.)
FCS (Check Sum) Error
Noise caused data corruption during
communication.
Carry out grounding work in accordance with the
conditions. (Refer to
Grounding in section 3 in the
Setup Manual.)
The PC is transmitting incorrect
data.
Check the operation at the host side.
Time-out Error
The connecting cables are not
connected correctly. (Send/Receive)
Check the communication cable connection and
perform a conductivity test. If there is a fault,
replace the cable.
For details on communication cables, refer to
Connecting to the Host from the RS-232C Port in
section 4 or
Connecting to the Host from the
RS-422A/485 Port in section 5 in the Setup Manual.
The communication service of the
host is stopped. (Send/Receive)
Check that the host is capable of communicating
with the PT (confirm that the communication
settings of the host and PT match).
Time-out Interval is too short. (Send)
Set a longer value for Time-out Interval at the host
side.
Time-out Interval is too short.
(Receive)
Set a longer value for Time-out Interval in the
System Menu. (Refer to
Setting the Time-out
Interval in section 6 in the Setup Manual.) It may
also be possible to solve the problem by shortening
the host cycle time.
PC Unit No. Error
The unit # does not match that set
on the PC.
Re-set the unit number at the host side to 0.
Noise caused data corruption during
communication.
Carry out grounding work in accordance with the
conditions. (Refer to
Grounding in section 3 in the
Setup Manual.)
NAK received
——
Check the settings for allocated words and bits.
If noise is a possible factor, distance the cable from
sources of noise and insert a noise filter in the
power supply line.
If using the equipment in a location subject to a lot
of noise, use a cable with a high degree of
protection against noise for the transmission route.
Also make the cable as short as possible.
Undefined Command
E
The host is not supported.
Check the PC model used for the host.
Error
Instruction level 3 is not effective.
Check that the instruction level setting for the host is
level 1, 2, 3.
Probable Causes and
Remedies
electronic components distributor
Содержание NT21 Series
Страница 3: ...iv Downloaded from Elcodis com electronic components distributor...
Страница 5: ...vi Downloaded from Elcodis com electronic components distributor...
Страница 367: ...3 12 Section Enabling Disabling PT Operations 358 Downloaded from Elcodis com electronic components distributor...
Страница 399: ...4 4 Section Memory Link Online Transfer Function 390 Downloaded from Elcodis com electronic components distributor...
Страница 431: ...6 2 Section Responding to Displayed Error Messages 422 Downloaded from Elcodis com electronic components distributor...
Страница 463: ...Downloaded from Elcodis com electronic components distributor...
Страница 465: ...Downloaded from Elcodis com electronic components distributor...