6-3
Section
Allocating PT Memory to the Host (Master)
78
Data Areas for Remote I/O Communications
Item
Master model
Fixed Allocation
(Without Configurator)
Free Allocation
(With Configurator)
Maximum number of
CVM1/CV-series
63 nodes
Slaves per Master
CS1-series,
C200HX/HG/HE
50 nodes
63 nodes
C200HS
32 nodes
63 nodes
Maximum number of
controlled I/O points
CVM1/CV-series
2,048 points (64 input words and
64 output words)
6,400 points (100 words
×
4 blocks)
per Master
CS1-series,
C200HX/HG/HE
1,600 points (50 input words and
50 output words)
4,800 points (without messaging)
1,600 points (with messaging)
C200HS
1,024 points (32 input words and
32 output words)
1,280 points
Maximum number of
CVM1/CV-series
32 input words and 32 output words
I/O points in Slave
controlled by Master
CS1-series,
C200HX/HG/HE
C200HS
Remote I/O allocation
area
CVM1/CV-series
Input: CIO 2000 to CIO 2063
Output: CIO 1900 to CIO 1963
CV500/CVM1-CPU01 (-V
j
)
CIO: 0000 to 2427
G: G008 to G255
DM: D00000 to D08191
Other PCs:
CIO: 0000 to 2555
G: G008 to G255
DM: D00000 to D24575
CS1-series,
C200HX/HG/HE
CS1-series PCs:
Input: CIO 0350 to CIO 0399
Output: CIO 0050 to CIO 0099
C200HX/HG/HE:
Input: IR 350 to IR 399
Output: IR 50 to IR 99
CS1-series PCs
CIO: 0000 to 0235, 0300 to 0511
HR: HR000 to HR099
CIO: 1000 to 1063 (see note)
DM: D00000 to D05999
C200HE-CPU11(-Z)
IR: 0000 to 0235, 0300 to 0511
HR: HR000 to HR099
LR: LR00 to LR63
DM: DM0000 to DM4095
Other C200HX/HG/HE PCs
IR: 0000 to 0235, 0300 to 0511
HR: HR000 to HR099
LR: LR00 to LR63
DM: DM0000 to DM5999
C200HS
Input: IR 350 to IR 381
Output: IR 50 to IR 81
IR: 0000 to 0235, 0300 to 0511
HR: HR000 to HR099
LR: LR00 to LR63
DM: D00000 to D05999
Note When LR 00 to LR 63 are allocated in CS1-series PCs with the Configurator, the
actual words allocated are CIO 1000 to CIO 1063.
When free (user-set) allocation is used, up to 4 blocks (2 output blocks and 2
input blocks of up to 100 words each) can be set in the areas listed in the table
above.
Reference There are limits on free allocation in CS1-series PCs. Follow the limits shown in
the table above.
This section explains how to connect the DeviceNet network properly.
Reference Only the basic connection procedures are explained here. Refer to the Device-
Net (CompoBus/D) Operation Manual (W267) for more details.
Registering the Remote
I/O Allocation Area