![Omron NC1-510000 Скачать руководство пользователя страница 139](http://html1.mh-extra.com/html/omron/nc1-510000/nc1-510000_user-manual_742744139.webp)
5-8-1
Connect UPS Using the USB Connector
The Power Attendant Lite Utility software monitors the UPS status via the USB interface and shuts
down the AMR Controller when needed.
UPS Drivers and the required software is available.
• For AMR Controllers with Windows 10 or Windows 7 preinstalled:
• Drivers for the S8BA UPS are pre-installed
• Installation files and manual for the Power Attendant Lite Utility are available in the directory
D:\OMRON-NY\Installers\
Power Attendant Lite Utility
• Installation files and manual for the UPS Settings Utility are available in the directory
D:\OMRON-NY\Installers\
UPS Settings Utility
• For all other AMR Controllers following software can be downloaded:
• Drivers for the S8BA UPS from this OMRON website.
• Installation files and manual for the Power Attendant Lite Utility from this OMRON website.
• Installation files and manual for the UPS Settings Utility (Windows only) from this OMRON web-
Precautions for Safe Use
• Always use an uninterruptible power supply (UPS) to prevent data loss and other system file
integrity issues caused by unexpected power interruption.
• Use an Omron S8BA UPS with the correct revision number to prevent improper system shut-
down.
• Correctly perform wiring and setting, and ensure that the shutdown by the UPS can be exe-
cuted.
Follow the steps below to connect the S8BA UPS with a USB cable and to configure it correctly.
Refer to
on page 3-27 for more information.
1
Ensure the revision number of the UPS is correct.
Refer to
on page 3-27 for more information.
2
For AMR Controllers that do not have Windows pre-installed: Download the above mentioned
software.
3
Wire the S8BA UPS.
1) Wire the input of the UPS to the output of the Power Supply.
2) Wire the output of the UPS to the power connector of the AMR Controller.
3) Ground the UPS.
4) Connect the USB port of the S8BA UPS to the USB port of the AMR Controller using the
USB cable provided with the S8BA UPS.
5 Installation
5-41
AMR Controller User's Guide (I650)
5-8 Connect UPS
5
5-8-1
Connect UPS Using the USB Connector
Содержание NC1-510000
Страница 1: ...AMR Controller User s Guide NC1 510000 NC1 510001 AMR Controller I650 E 01...
Страница 4: ...Introduction 2 AMR Controller User s Guide I650...
Страница 36: ...1 Overview 1 6 AMR Controller User s Guide I650...
Страница 156: ...7 Maintenance 7 8 AMR Controller User s Guide I650...
Страница 183: ...I Index I 1 AMR Controller User s Guide I650 I...
Страница 186: ...Index I 4 AMR Controller User s Guide I650...
Страница 187: ......