K8DT-AW

7

Setting Method

Setting Current

The current knobs (AL1, AL2) are used to set the current.
The current can be set to 10% to 100% of the maximum setting range.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the 
same level.)
Use this as a guide to set the current.
The maximum setting range will differ depending on the model and the input terminal.
Example: K8DT-AW3 Using Input Terminals I3-COM
The maximum measuring current will be 200 A AC and the setting range will be 20 to 200 A.

Operating Time

The operating time is set using the operating time knob (T).
The operating time can be set to between 0.1 and 30 s.
If the input current exceeds (drops lower than) the set value, the alarm indicator will start flashing for the set period and then stay lit.

Startup Lock Time

The startup lock time is set using the startup lock time knob (LOCK).
The startup lock time can be set to between 0 and 30 s.
The startup lock time will start when the input current reaches 30% or more of the set value.
Use startup lock time to prevent unwanted operation, e.g., as a result of inrush current.

Note:

This function is valid only for overcurrent operation.

Errors are not detected 
during this time.

Startup lock time

Startup lock timer start

30% of current set value

Current set value

Inrush current

Содержание K8DT-AW Series

Страница 1: ...tions Order Separately Front Cover Refer to Safety Precautions on page 10 Refer to page 9 for commonly asked questions Setting range Power supply voltage Output Model 2 to 20 mA AC DC 10 to 100 mA AC...

Страница 2: ...COM 2 to 20 mA AC DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 100 mA AC DC I2 COM 10 to 100 mA AC DC Approx 1 500 mA AC DC I3 COM 50 to 500 mA AC DC Approx 0 2 K8DT AW...

Страница 3: ...5 to 1 5 mm2 AWG24 to AWG16 Wire insertion force 8 N max for AWG20 wire Screwdriver insertion force 15 N max Wire stripping length 8 mm Ferrule length 8 mm Current capacity 10 A per pole Number of ins...

Страница 4: ...copper wires with a rating of 75 C or an equivalent rating 1 Current Input AW1 3 Power Supply Voltage A 100 to 240 VAC D 24 VAC DC No polarity 500 mA max 20 mA max 100 mA max AW2 AW3 CT 100 A max CT...

Страница 5: ...AL1 alarm indicator AL2 alarm indicator Contacts 11 14 or transistor output Overcurrent set value AL2 Overcurrent set value AL1 Input Power supply voltage LOCK t t LOCK Startup lock time 0 to 30 s t O...

Страница 6: ...pen the DIP switch cover to set the DIP switch Keep the DIP switch cover closed while the power supply to the Relay is ON Model Setting range Input type Wiring connections K8DT AW1 2 to 20 mA AC DC Di...

Страница 7: ...ating Time The operating time is set using the operating time knob T The operating time can be set to between 0 1 and 30 s If the input current exceeds drops lower than the set value the alarm indicat...

Страница 8: ...5 13 5 86 54 63 11 4 7 Four M4 6 screws 17 20 9 3 1 7 1 7 9 3 76 OMRON CT K8AC CT200L Mounting Hole Dimensions Note The OMRON Current Transformer CT is designed to be used with the K8DT AW3 Use termin...

Страница 9: ...tely 30 A The startup current will exceed the overload capacity rating 150 for 1 s of the K8DT AW1 and K8DT AW2 and result in failure of the Relay To monitor the motor load use the K8DT AW3 Overload c...

Страница 10: ...ails monitoring and alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay reg...

Страница 11: ...supply power to the product 22 Do not install the product immediately next to heat sources 23 Perform periodic maintenance 24 Do not wire anything to the release holes 25 When you insert a flat blade...

Страница 12: ...rom the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block To prevent short ci...

Страница 13: ...re is basic insulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic insulation between the in...

Страница 14: ...MEMO 14...

Страница 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 16: ...IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron...

Отзывы: