Checking Operation

Overcurrents
Gradually increase the input from 80% of the set value.
The input will equal the operating value when the input 
exceeds the set value and the alarm indicator starts flashing. 
Operation can be checked by the relay outputs that will start 
after the operating time has passed.
Undercurrent
Gradually decrease the input from 120% of the set value and 
check the operation using the same method as for 
overcurrent.

How to Measure the Operating Time

Overcurrent
Change the input suddenly from 0% to 120% of the set value 
and measure the time until the Unit operates.
Undercurrent
Change the input suddenly from 120% to 0% of the set value 
and measure the time until the Unit operates.

Monitoring Switch-mode Power Supplies

Switch-mode Power Supplies cannot be monitored. In circuits 
with a capacitor input, including switch-mode power supplies, 
the input capacitor recharge current flows in pulse form as the 
load current. The K8DT-AW

@

 has a built-in filter as a 

countermeasure against high frequencies and cannot be 
used to remove pulse current.

Can a motor with a rated current of 5 A be moni-
tored using the K8DT?
Are there any application precautions?

The K8DT-AW1 and K8DT-AW2 cannot be used with motor 
loads. Use the K8DT-AW3 in combination with the K8AC-
CT200L Current Transformer (CT). With motor loads, the 
startup current and stall current will cause a current of many 
times the rated current to flow. Refer to the following figure for 
information on the motor startup current.

For a motor with a rating of 5 A, the startup current will be 
approximately 30 A. The startup current will exceed the 
overload capacity (rating: 150% for 1 s) of the K8DT-AW1 and 
K8DT-AW2 and result in failure of the Relay. 
To monitor the motor load, use the K8DT-AW3. (Overload 
capacity: 120% of rating for continuous load, 200% of rating 
for 30 s, and 600% of rating for 1 s).
The K8DT-AW3 has a large input range. Pass the conductors 
multiple times through the special CT.

Concept behind Passing Conductor through the CT When 
Using the K8DT-AW3

Example: Monitoring Overload of a Motor with a Rated Current of 5 A

K8DT set value: 
Overcurrent detection, operating value setting: 25%, operating time: 0.1 s
Startup lock timer: 0.1 to 30 s (Set the timer according to the duration 
of the startup current.) 

The setting range for the K8DT-AW3 is 10% to 100% of the rated 
current (i.e., 10 to 100 A). Pass the conductors through the CT five 
times so that at least 10 A of current flows. The input current to the 
K8DT will be 25 A (i.e., 5 A x 5 loops).
If a startup current of six times the rated current is generated, it will be 
150 A (i.e., 25 A x 6). The overload capacity for the K8DT-AW3 is 
200% of the rating for 30 s. The Relay will not fail even if the startup 
current continues for 30 s, and it is possible to perform overload 
detection.

Questions and Answers

Q

Current input

Set value

Alarm indicator

Flashing

5 s

Lit

Contact output or 

transistor output

A1

Output

Input terminals

Power

supply

A2

±

C

100 VAC

100 VAC

100V

A

Cycle counter

0 to 10 A

30 

Ω

400 W (two in parallel)

Variable autotransformer

Example: Overcurrent Operating Mode, Normally Closed Relay 
Drive, and an Operating Time of 5 s.

Connection Diagram

Q

Q

Q

Several seconds to 
several tens of seconds

Time from beginning of startup

100%

500%

Motor current (percentage of r

ated v

alue)

K8AC-CT200L

Primary-side conductor

To the K8DT-AW3

Содержание K8DT-AW Series

Страница 1: ...tions Order Separately Front Cover Refer to Safety Precautions on page 10 Refer to page 9 for commonly asked questions Setting range Power supply voltage Output Model 2 to 20 mA AC DC 10 to 100 mA AC...

Страница 2: ...COM 2 to 20 mA AC DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 100 mA AC DC I2 COM 10 to 100 mA AC DC Approx 1 500 mA AC DC I3 COM 50 to 500 mA AC DC Approx 0 2 K8DT AW...

Страница 3: ...5 to 1 5 mm2 AWG24 to AWG16 Wire insertion force 8 N max for AWG20 wire Screwdriver insertion force 15 N max Wire stripping length 8 mm Ferrule length 8 mm Current capacity 10 A per pole Number of ins...

Страница 4: ...copper wires with a rating of 75 C or an equivalent rating 1 Current Input AW1 3 Power Supply Voltage A 100 to 240 VAC D 24 VAC DC No polarity 500 mA max 20 mA max 100 mA max AW2 AW3 CT 100 A max CT...

Страница 5: ...AL1 alarm indicator AL2 alarm indicator Contacts 11 14 or transistor output Overcurrent set value AL2 Overcurrent set value AL1 Input Power supply voltage LOCK t t LOCK Startup lock time 0 to 30 s t O...

Страница 6: ...pen the DIP switch cover to set the DIP switch Keep the DIP switch cover closed while the power supply to the Relay is ON Model Setting range Input type Wiring connections K8DT AW1 2 to 20 mA AC DC Di...

Страница 7: ...ating Time The operating time is set using the operating time knob T The operating time can be set to between 0 1 and 30 s If the input current exceeds drops lower than the set value the alarm indicat...

Страница 8: ...5 13 5 86 54 63 11 4 7 Four M4 6 screws 17 20 9 3 1 7 1 7 9 3 76 OMRON CT K8AC CT200L Mounting Hole Dimensions Note The OMRON Current Transformer CT is designed to be used with the K8DT AW3 Use termin...

Страница 9: ...tely 30 A The startup current will exceed the overload capacity rating 150 for 1 s of the K8DT AW1 and K8DT AW2 and result in failure of the Relay To monitor the motor load use the K8DT AW3 Overload c...

Страница 10: ...ails monitoring and alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay reg...

Страница 11: ...supply power to the product 22 Do not install the product immediately next to heat sources 23 Perform periodic maintenance 24 Do not wire anything to the release holes 25 When you insert a flat blade...

Страница 12: ...rom the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block To prevent short ci...

Страница 13: ...re is basic insulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic insulation between the in...

Страница 14: ...MEMO 14...

Страница 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 16: ...IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron...

Отзывы: