Omron K8DT-AW Series Скачать руководство пользователя страница 5

K8DT-AW

5

Timing Charts

Overcurrent and Undercurrent Operation Diagram

DIP switch settings: SW3 ON and SW4 ON, or 
SW3 OFF and SW4 OFF

Overcurrent and Overcurrent Operation Diagram 

DIP switch settings: SW3 ON and SW4 OFF.

Undercurrent and Undercurrent Operation Diagram 

DIP switch settings: SW3 OFF and SW4 ON.

Nomenclature

Front

Note:

Use solid wires, stranded wires, or ferrules to connect to the 
terminals.
To maintain the withstand voltage after connecting the 
terminals, insert 8 mm of exposed conductor into the terminal. 

Indicators

Setting Knobs

Input

Note 1. The K8DT-AW

@

 outputs are normally operative.

Note 2. The startup lock prevents unnecessary alarms from being generated during the unstable period 

when the power is first turned ON. This function is valid only for overcurrent operation.

Delay time: 250 ms 
(reference value)

Delay time: 250 ms 
(reference value)

t

Flashing

Lit

Flashing

Lit

Hysteresis: Fixed at 5%

Hysteresis: Fixed at 5%

AL1 alarm indicator

AL2 alarm indicator

Contacts 11-14 or 

transistor output

Overcurrent 

set value (AL1)

Undercurrent 

set value (AL2)

Power 

supply voltage

t: Operating time (0.1 to 30 s)

LOCK

LOCK: Startup lock time (0 to 30 s)

t

t: Operating time (0.1 to 30 s)

Note 1. The K8DT-AW

@

 outputs are normally operative.

Note 2. The startup lock prevents unnecessary alarms from being generated during the 

unstable period when the power is first turned ON. This function is valid 
only for overcurrent operation.

Delay time: 250 ms 
(reference value)

Delay time: 250 ms 
(reference value)

Flashing

Lit

Flashing

Lit

Hysteresis: Fixed at 5%

Hysteresis: Fixed at 5%

AL1 alarm indicator

AL2 alarm indicator

Contacts 11-14 or 

transistor output

Overcurrent 

set value (AL2)

Overcurrent 

set value (AL1)

Input

Power 

supply voltage

LOCK

t

t

LOCK: Startup lock time (0 to 30 s)

t: Operating time (0.1 to 30 s)

Note 1. The K8DT-AW

@

 outputs are normally operative.

Note 2. The startup lock prevents unnecessary alarms from being generated during the unstable period 

when the power is first turned ON. This function is valid only for overcurrent operation.

Delay time: 250 ms 
(reference value)

Delay time: 250 ms 
(reference value)

Lit

Flashing

Lit

Hysteresis: Fixed at 5%

Hysteresis: Fixed at 5%

AL1 alarm indicator

AL2 alarm indicator

Contacts 11-14 or 

transistor output

Undercurrent 

set value (AL2)

Input

Undercurrent 

set value (AL1)

Power 

supply voltage

Flashing

LOCK

t

t

LOCK: Startup lock time (0 to 30 s)

t: Operating time (0.1 to 30 s)

Current knob (AL1)

Current knob (AL2)

Operating time knob (T)

Startup lock time knob
(LOCK)

Terminal block

 (See note.)

Terminal block

 (See note.)

Power indicator

Output status indicator

Alarm indicator

8 mm

8 mm

Solid Wire

8 mm

Stranded Wires

Ferrules

Item

Meaning

Power indicator 
(PWR: Green)

Lit when power is being supplied.

Output status indicator 
(Output: Yellow)

Lights for output (lit for normal operation)

Alarm indicator 
(ALM1, ALM2: Red)

Lit when there is an overcurrent or undercurrent. 
The indicator flashes to indicate the error status 
after the input has exceeded the set value while 
the operating time is being clocked. 

Item

Usage

Current knob (AL1)

Used to set the current to 10% to 100% of 
maximum setting range.

Current knob (AL2)

Used to set the current to 10% to 100% of 
maximum setting range.

Operating time knob (T)

Used to set the operating time to 0.1 to 30 s.

Startup lock time knob 
(LOCK)

Used to set the startup lock time to 0 to 30 s.

Содержание K8DT-AW Series

Страница 1: ...tions Order Separately Front Cover Refer to Safety Precautions on page 10 Refer to page 9 for commonly asked questions Setting range Power supply voltage Output Model 2 to 20 mA AC DC 10 to 100 mA AC...

Страница 2: ...COM 2 to 20 mA AC DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 100 mA AC DC I2 COM 10 to 100 mA AC DC Approx 1 500 mA AC DC I3 COM 50 to 500 mA AC DC Approx 0 2 K8DT AW...

Страница 3: ...5 to 1 5 mm2 AWG24 to AWG16 Wire insertion force 8 N max for AWG20 wire Screwdriver insertion force 15 N max Wire stripping length 8 mm Ferrule length 8 mm Current capacity 10 A per pole Number of ins...

Страница 4: ...copper wires with a rating of 75 C or an equivalent rating 1 Current Input AW1 3 Power Supply Voltage A 100 to 240 VAC D 24 VAC DC No polarity 500 mA max 20 mA max 100 mA max AW2 AW3 CT 100 A max CT...

Страница 5: ...AL1 alarm indicator AL2 alarm indicator Contacts 11 14 or transistor output Overcurrent set value AL2 Overcurrent set value AL1 Input Power supply voltage LOCK t t LOCK Startup lock time 0 to 30 s t O...

Страница 6: ...pen the DIP switch cover to set the DIP switch Keep the DIP switch cover closed while the power supply to the Relay is ON Model Setting range Input type Wiring connections K8DT AW1 2 to 20 mA AC DC Di...

Страница 7: ...ating Time The operating time is set using the operating time knob T The operating time can be set to between 0 1 and 30 s If the input current exceeds drops lower than the set value the alarm indicat...

Страница 8: ...5 13 5 86 54 63 11 4 7 Four M4 6 screws 17 20 9 3 1 7 1 7 9 3 76 OMRON CT K8AC CT200L Mounting Hole Dimensions Note The OMRON Current Transformer CT is designed to be used with the K8DT AW3 Use termin...

Страница 9: ...tely 30 A The startup current will exceed the overload capacity rating 150 for 1 s of the K8DT AW1 and K8DT AW2 and result in failure of the Relay To monitor the motor load use the K8DT AW3 Overload c...

Страница 10: ...ails monitoring and alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay reg...

Страница 11: ...supply power to the product 22 Do not install the product immediately next to heat sources 23 Perform periodic maintenance 24 Do not wire anything to the release holes 25 When you insert a flat blade...

Страница 12: ...rom the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block To prevent short ci...

Страница 13: ...re is basic insulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic insulation between the in...

Страница 14: ...MEMO 14...

Страница 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 16: ...IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron...

Отзывы: