K8AK-AS

4

Connections

Wiring Diagram

Overcurrent Operation Diagram 

(Output Relay Drive Method: Normally Open)

DIP switch setting: SW3 OFF.

Undercurrent Operation Diagram 

(Output Relay Drive Method: Normally Closed)

DIP switch setting: SW3 ON.

Note: 1.

The K8AK-AS3 is designed to be used in combination with 

the OMRON K8AC-CT200L Current Transformer (CT).

2.

There is no polarity when a DC current input is used.

3.

Refer to the 

Setting Ranges and Wiring Connections

 as the 

explanation of current input l1, l2, and l3 terminal.

AS (I3 terminal)

0

10

10

60

50

40

30

20

5

15

Distance between products d [mm]

I = 3 A

I = 5 A

I = 1 A

I = 8 A

Ambient temperature [°C]

K8AK

No.3

K8AK

No.2

K8AK

No.1

K8AK

No.4

K8AK

No.5

DIN Track

Distance between products: d

Sample: K8AK-AS

Applied voltage: 240 VAC 

Mounting distances: 0, 5, and 10 mm min.

Test method

Relationship of Mounting Distance between 

K8AK-AS Relays and Input Current 

(Reference Values)

The following diagram shows the relationship between the mounting 

distances and the input current. If the relay is used with an input 

current that exceeds these values, the temperature of the K8AK may 

rise and shorten the life of the internal components.

Power supply 

voltage

Set value

Input

Alarm indicator

Relay 11-14

Relay 11-12

Hysteresis

(

5% to 50% of operating value)

Lit

Flashing

T: Operating time (0.1 to 30 s)

Lock: Startup lock time (0 to 30 s) 

LOCK

T

Power supply

voltage

Set value

Input

Relay 11-14

Relay 11-12

Alarm indicator

Lit

Flashing

Hysteresis

(5% to 50% of operating value)

T

T: Operating time (0.1 to 30 s)

Single-phase power

A1

Power supply

voltage

A2

Current 

input

I1
I2
I3
COM

14

Signal 

output

12

A1

A2

Current 

input

I1
I2
I3
COM

14

Signal 

output

12

Relay 

signal

output

or

Load

Single-phase power

Relay 

signal

output

Load

11

11

Power supply

voltage

Содержание K8AK-AS

Страница 1: ...ble Accessory Order Separately OMRON CT Commercially Available CTs If you use a commercially available CT do notexceed the overload capacity of the K8AK AS2 Refer to Safety Precautions for the K8AK Se...

Страница 2: ...K8AK AS2 0 1 to 1 A AC DC Compatible with commercially available CTs 0 5 to 5 A AC DC Compatible with commercially available CTs 0 8 to 8 A AC DC K8AK AS3 When used with the OMRON CT K8AC CT200L 10 t...

Страница 3: ...humidity rated power supply voltage DC or 50 60 Hz sine wave input Operating time 50 ms at 25 C and 65 humidity rated power supply voltage Applicable standards Conforming standards EN60947 5 1 Install...

Страница 4: ...5 and 10 mm min Test method Relationship of Mounting Distance between K8AK AS Relays and Input Current Reference Values The following diagram shows the relationship between the mounting distances and...

Страница 5: ...e notes 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when relay is operating Alarm indicator AL...

Страница 6: ...input terminal Example K8AK AS3 Using Input Terminals I3 COM The maximum setting range will be 200 A AC and the setting range will be 20 to 200 A 2 Hysteresis Hysteresis is set using the hysteresis k...

Страница 7: ...lashes when the set value and the input have reached the same level Use this as a guide to set the startup lock time The startup lock time will start when the input current reaches 30 or more of the s...

Страница 8: ...ure for information on the motor startup current For a motor with a rating of 5 A the startup current will be approximately 30 A The startup current will exceed the overload capacity rating 150 for 1...

Страница 9: ...s 2 Use and store the product in a location where the ambient temperature and humidity are within the specified ranges If applicable provide forced cooling 3 Mount the product in the correct direction...

Страница 10: ...will be large if the K8AK AS K8AK AW K8AK VS or K8AK VW is used for thyristor or inverter control The K8AK PH K8AK PA K8AK PM K8AK PW or K8DS PH cannot be used on the secondary side of an inverter To...

Страница 11: ...nt or addition to the above warranty See http www omron247 com or contact your Omron representative for pub lished information 14 Limitation on Liability Etc OMRON COMPANIES SHALL NOT BE LIABLE FOR SP...

Страница 12: ...rasil 55 11 2101 6300 www omron com br OMRON ARGENTINA SALES OFFICE Cono Sur 54 11 4783 5300 OMRON CHILE SALES OFFICE Santiago 56 9 9917 3920 OTHER OMRON LATIN AMERICA SALES 54 11 4783 5300 OMRON INDU...

Отзывы: