background image

K3TJ

K3TJ

13

8. Display Brightness Adjustment

It is possible to change the display brightness in three steps.

Use the Up or Down Key to select the
proper display brightness.

Up Key or
Down Key

1

3
4
5
6
7
8

2

OFF

ON

Set parameter selector pin 8 to ON, at
which time the display will not change
but a display brightness adjustment will
be possible.

After the display brightness has been
selected, set parameter pin 8 to com-
plete the display brightness setting.

1

3
4
5
6
7
8

2

OFF

ON

Error Message

Refer to the following table in the case of an error.

Display

Cause

Remedy

e 01

The internal memory has malfunctioned.

Turn the K3TJ OFF and ON. If the error condition of the
K3TJ does not change consult your OMRON representative

e 02

The non-volatile memory has malfunctioned.

K3TJ does not change, consult your OMRON representative.

e 03

The calibration value stored in the non-volatile memory has
been corrupted.

e 10

The input range set value stored in the non-volatile memory
has been corrupted.

Select the input range again according to the input range
setting procedure.

e 11

The shift value stored in the non-volatile memory has been
corrupted.

Execute display shift again according to the display shift
adjustment procedure.

e 12

The scaling value stored in the non-volatile memory has
been corrupted.

Execute scaling again according to the scaling adjustment
procedure.

e 13

The decimal point set value stored in the non-volatile
memory has been corrupted.

Set the decimal point again according to the decimal point
setting procedure.

e 14

The average processing set value stored in the non-volatile
memory has been corrupted.

Select average processing again according to the average
processing setting procedure.

e 15

The zero limit value stored in the non-volatile memory has
been corrupted.

Set the zero limit value again according to the zero limit
value setting procedure.

e 16

The step value stored in the non-volatile memory has been
corrupted.

Set the step display pattern again according to the step
display setting procedure.

e 17

The brightness setting value in the non-volatile memory has
been corrupted.

Set the display brightness again according to the display
brightness adjustment procedure.

Note:

Turn the K3TJ OFF and ON while pressing both the Up and Down Keys so that the K3TJ’s shifting and scaling settings will return to the
ones preset before shipping.

Содержание K3TJ

Страница 1: ...htness can be adjusted Conforms to the EMC standard EN61010 1 IEC1010 1 uC Ordering Information DC Voltage Input Model Voltage measurement range Display color Supply voltage g g p y 100 to 240 VAC 24...

Страница 2: ...nce Malfunction 10 to 55 Hz 0 5 mm single amplitude for 10 minutes each in X Y and Z directions Destruction 10 to 55 Hz 0 75 mm single amplitude for 2 hours each in X Y and Z directions Shock resistan...

Страница 3: ...panel meets the requirements of IP50 instead Measuring Ranges Measuring range Input impedance Reliability Max permissible continuous load Voltage DC 1 to 5 VDC 1 M 0 1 rdg 1 digit 250 V g 0 to 5 VDC 1...

Страница 4: ...iver into the groove on the bottom of the front panel and pull the front panel off The following is seen after the front panel is removed Parameter selector Up Key Down Key 1 34 5 6 7 8 2 ON No Name P...

Страница 5: ...o 1000 0 to 10 VDC input DC Current Input Model Input range Display 4 to 20 mA DC input 0 to 1000 1000 0 max min Display Input Adjust the display shift and scaling for the K3TJ while applying an actua...

Страница 6: ...the display To change the value to 0 use the Down Key The displayed value will increase automatically if the Up Key is pressed for 1 s or more and will decrease automatically if the Down Key is press...

Страница 7: ...er selector pin 3 to ON at which time the display will not change but a scaling adjustment will be possible After 1200 is displayed set parameter selector pin 3 to OFF to complete the scaling adjustme...

Страница 8: ...gntimes This methodis effectivewhentheuserrequiresa long display refresh period Inmovement averageprocessing method the samplingdata obtainedfrom samplingn times including thepresent samplingoperation...

Страница 9: ...mit setting range off No zero limit factory set Zero Limit Setting Range Display Zero limit setting value Input 7 Step Display Setting Step display setting is used to change the step of the displayed...

Страница 10: ...alue stored in the non volatile memory has been corrupted Execute display shift again according to the display shift adjustment procedure e 12 The scaling value stored in the non volatile memory has b...

Страница 11: ...ections 24 VDC HOLD GND GND 0 to 10 VDC 0 to 5 VDC 1 to 5 VDC 4 to 20 mA DC INPUT POWER 3 2 1 4 5 6 7 8 9 100 to 240 VAC Note Terminals 3 and 6 are connected internally The power supply terminals are...

Страница 12: ...le Never use the K3TJ in locations where corrosive gas particularly sulfuric or ammonia gas exists Avoid use of the K3TJ in locations subject to severe shock or vibra tion excessive dust or excessive...

Страница 13: ...n Phone 06 949 6012 Fax 06 949 6021 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No N080 E1 1C In...

Отзывы: