Upper Limit (H) of Linear Output Range
Lower Limit (L) of Linear Output Range
Linear output setting is made in the option menu to enable the K3NX to have
voltage or current output in proportion to the change in display value.
•
The maximum and minimum values of linear output are set in this parameter.
Linear output
20 mA or 5 V
Display value
4 mA or 1 V
•
L can be greater or less than H.
•
L cannot be the same as H, otherwise H will be automatically set to a value
obtained by adding 1 to L.
•
The teaching function can be used for setting linear output ranges.
Input type
Setting range
Default
DC voltage input
–19999 to 99999
H linear output range
199.99
L linear output range
–199.99
DC current input
–19999 to 99999
H linear output range
199.99
L linear output range
–199.99
AC voltage input
–19999 to 99999
H linear output range
400.0
L linear output range
0.0
AC current input
–19999 to 99999
H linear output range
10.000
L linear output range
0.000
Refer to 5-1 Teaching Function.
This setting is available for the K3NX with the Linear Output Board.
lset.h
lset.l
FUNCTION
SETTING
REFERENCE