62
Thermal Overload Relay
J7TKN
Temperature Compensation
In case of higher ambient temperature use the following formula:
(Ambient temperature - 20) x 0.125 = correction factor in % of the
full load motor current
Example:
Ambient temperature 70°C, full load motor current 7A
(70 - 20) x 0.125 = 6.25%
Setting value: 7A + 6,25% = 7.44A
■
Dimensions
Data according to
C
UL
US
Type
J7TKN-A
J7TKN-B
J7TKN-C
J7TKN-D
J7TKN-E
Rated insulation voltage
V~
600
600
600
600
600
Rated current
A
23
32
42
74
85
Auxiliary contacts
Rated voltage
same potential
V AC 600
600
600
600
600
different potential
V~
150
150
150
150
150
Switching capacity
AC
VA
500
500
600
600
600
of aux. contacts
A
4
2
4
4
4
J7KNA-09 + J7TKN-A
J7KNA-12
J7KN-10 + J7TKN-B
J7KN-14
J7KN-18
J7KN-22
J7KNG-10 D+ J7TKN-B
J7KNG-14 D
J7KNG-18 D
J7KNG-22 D
J7KN-24 + J7TKN-B
J7KN-32
J7KN-40