Motor Contactor
J7KN
47
Contactors for North America
Data according to UL508
Main Contacts (cULus)
Type
J7KN-10
J7KN-14
J7KN-18
J7KN-22
J7KN-24
J7KN-32
J7KN-40
J7KN-50
J7KN-62
J7KN-74
Rated operational current
"General Use"
A
25
25
30
30
50
65
80
110
120
130
Rated operational power
110-120V hp
1½
2
2
3
5
5
7½
10
10
10
of three-phase motors
200V hp
3
3
5
5
7½
10
10
15
20
25
at 60Hz (3ph)
220-240V hp
3
3
7½
7½
10
10
15
20
25
30
277V hp
3
5
7½
7½
7½
10
15
20
25
30
380-415V hp
5
5
10
10
10
15
20
25
30
40
440-480V hp
5
7½
10
15
15
20
25
30
40
50
550-600V hp
7½
10
15
20
20
25
30
40
50
50
Rated operational power
110-120V hp
½
¾
1
1½
1½
2
3
3
5
7½
of AC motors
200V hp
1
1,5
2
3
3
5
7½
7½
10
15
at 60Hz (1ph)
220-240V hp
1½
2
3
3
5
5
7½
10
15
15
277V hp
2
3
3
5
5
7½
10
10
15
15
380-415V hp
3
3
5
5
5
7½
10
15
20
20
440-480V hp
3
5
5
7½
7½
10
15
20
25
25
550-600V hp
3
5
7½
10
10
15
20
25
30
30
Rated operational power of
110-120V hp
-
-
-
-
2
3
-
3
5
-
three-phase motors at 60Hz (3ph)
200V hp
-
-
-
-
3
5
-
7½
10
-
for elevators
220-240V hp
-
-
-
-
5
7½
-
7½
10
-
Demands according to ANSI A17.5
(500.000 operations)
440-480V hp
-
-
-
-
10
15
-
20
25
-
550-600V hp
-
-
-
-
10
20
-
25
30
-
Rated operationalcurrent
600V A
-
-
-
-
15
22
-
27
37
-
Fuses
A
30
40
50
50
90
125
175
175
225
250
Suitable for use on a capability
of delivering not more than
rms A
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
(SCCR)
V
600
600
600
600
600
600
600
600
600
600
Auxiliary Contacts (cULus)
A600
A600
A600
A600
-
-
-
-
-
-
Main Contacts (cULus)
Type
J7KN-85
J7KN-110
J7KN-151
J7KN-176
J7KN-200
Rated operational current
"General Use"
A
125
125
180
220
-
Rated operational power
110-120V hp
15
-
-
-
-
of three-phase motors
200V hp
-
30
40
50
-
at 60Hz (3ph)
220-240V hp
35
40
50
60
-
277V hp
-
-
-
-
-
380-415V hp
-
-
-
-
-
440-480V hp
65
75
100
125
-
550-600V hp
85
100
125
150
-
Rated operational power
110-120V hp
8
10
15
25
-
of AC motors
200V hp
-
20
-
-
-
at 60Hz (1ph)
220-240V hp
20
20
25
30
-
277V hp
-
-
-
-
-
380-415V hp
-
-
-
-
-
440-480V hp
-
50
-
-
-
550-600V hp
-
60
-
-
-
Rated operational power of
110-120V hp
-
-
-
-
-
three-phase motors at 60Hz (3ph)
200V hp
-
-
-
-
-
for elevators
220-240V hp
-
-
-
-
-
Demands according to ANSI A17.5
(500.000 operations)
440-480V hp
-
-
-
-
-
550-600V hp
-
-
-
-
-
Rated operationalcurrent
600V A
-
62
-
-
-
Fuses
A
-
300
300
500
-
Suitable for use on a capability
of delivering not more than
rms A
10000
10000
10000
10000
-
(SCCR)
V
600
600
600
600
-
Auxiliary Contacts (cULus)
A600
A600
-
-
-