background image

H2F-D

2

Specifications

Time Specifications

Ratings

Note: 1.

Use the switch on the back of the H2F-D to change the frequency.

2.

Inrush current will briefly flow when the power supply is turned ON. For details, refer to 

Technical Guide for Timers and Time Switches

.

Characteristics

Note: 1.

Deviation in the ON time or OFF time. 

2.

Time difference between the set time and time required to start operation when the pointer is set to the present time.

3.

Value when power has been supplied for at least 72 h at initial use.

Type

Cycle

Minimum scale graduation Minimum set time

Maximum set time

Daily

24 h

15 min

15 min

23 h 45 min

Power supply voltage

Synchronous motor: 100/110/120 VAC, 50/60 Hz; 200/220/240 VAC, 50/60 Hz (See note 1.)
Quartz motor: 100 to 240 VAC, 50/60 Hz; 12 to 24 VDC

Operating voltage range

85% to 110% of rated supply voltage

Power consumption (See note 2.)

Synchronous motor: 3 VA max.
Quartz motor: 1 VA max. at 100 to 120 VAC, 4 VA max. at 200 to 240 VAC, 1 W max. at 12 to 24 VDC

Control output

15 A at 250 VAC, resistive load

Ambient operating temperature

10 to 55

°

C (with no icing)

Ambient operating humidity

35% to 85%

Type

Daily

Item

Synchronous motor

Quartz motor

Operating time deviation (See note 1.)
Voltage influence and temperature 
influence

±

3 min max.

Setting error (See note 2.)

±

3 min max.

Cyclic error

±

3 min max.

Power interruption backup time

---

180 h min. (See note 3.)

Insulation resistance

100 M

Ω

 min. (at 500 VDC)

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and non-current-carrying metal 
parts and between control output and operating circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)

Vibration resistance

Destruction

16.7 Hz with 2-mm single amplitude for 1 hour each in three directions

Malfunction

10 to 55 Hz with 0.25-mm single amplitude for 10 minutes each in three directions

Shock resistance

Destruction

1,000 m/s

2

 5 times each in 6 directions

Malfunction

200 m/s

2

 once each in 6 directions

Life expectancy

Contacts: 10,000 operations min., Motor: 20,000 h

Weight

Flush-mounting model: Approx. 150 g, Surface-mounting model: Approx. 200 g

Case color

Light gray (Munsell 5Y7/1)

Содержание H2F-D

Страница 1: ... models that have been certified for safety standards refer to your OMRON website Ordering Information Note Always use the Time Switch with the Y92S 42 Battery mounted Accessories Order Separately Control cycle Drive method Power interruption backup Power supply voltage Mounting method Flush mounting Surface mounting track mounting Control output SPST NO SPDT SPST NO SPDT Daily 24 hours Synchronou...

Страница 2: ... to 24 VDC Control output 15 A at 250 VAC resistive load Ambient operating temperature 10 to 55 C with no icing Ambient operating humidity 35 to 85 Type Daily Item Synchronous motor Quartz motor Operating time deviation See note 1 Voltage influence and temperature influence 3 min max Setting error See note 2 3 min max Cyclic error 3 min max Power interruption backup time 180 h min See note 3 Insul...

Страница 3: ... F Location of yellow lever Flush Mounting Surface Mounting DIN Track Mounting 72 72 45 mm H W D below faceplate 29 mm 95 72 50 mm H W D Panel Cutout Dimensions according to DIN 43700 Panel thickness 1 to 3 2 mm Note The mounting adapter and mounting screws are enclosed Mounting Screw Dimensions Adapter 68 0 7 0 68 0 7 0 17 5 27 5 Screw size M3 45 enclosed 61 0 2 Two M3 60 0 2 ...

Страница 4: ...inal Nomenclature H2F D H2F DF H2F DC H2F DFC H2F DM H2F 30 H2F DMF Note On the H2F 30 12 to 24 VDC terminal number 2 is positive and terminal number 3 is negative H2F DMC H2F DMFC H2F 31 Note On the H2F 31 12 to 24 VDC terminal number 2 is positive and terminal number 3 is negative Mounting Holes ON OFF operation selector knob Dial rotation direction clockwise Manual switch Time setting knob Hole...

Страница 5: ...ll units are in millimeters unless otherwise indicated 72 72 65 5 45 65 5 1 3 17 16 H2F D C H2F DM C H2F 30 Note The terminal screws are M3 5 72 72 95 2 2 50 9 6 6 29 H2F DF C H2F DMF C H2F 31 Note The terminal screws are M3 5 ...

Страница 6: ... the manual switch is set to AUTO Load 1 terminals 4 and 5 will turn ON and load 2 terminals 5 and 6 will turn OFF when the manual switch is set to ON Check the output indicator when returning operation to AUTO If the knob has been touched or the output indicator has changed because of vibration or shock turn the knob switch the output and then return operation to AUTO Output Indicator and ON OFF ...

Страница 7: ... excessive discharge if the H2F is left unused for an extended period with the battery mounted Be sure to remove the battery before storing the H2F Turn OFF the power supply before replacing the battery Use only the specified battery Y92S 42 The battery may leak or burst if any other battery is used possibly resulting in equipment damage or injury Other Precautions Always use a thermo switch on th...

Страница 8: ...rther in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity with any standards codes or regulations which apply to the combination of the Product in the Buyer s application or use of the Product At Buyer s request Omron will provide applicable third party ce...

Отзывы: