manualshive.com logo in svg
background image

CONFIDENTIAL

©  OMRON  Corporation

0

GI-S series

How to configure a software IP address with a DHCP server 
application

SPD-1809139 Rev.B

Содержание GI-S series

Страница 1: ...CONFIDENTIAL OMRON Corporation 0 GI Sseries How to configure a software IP address with a DHCP server application SPD 1809139 Rev B...

Страница 2: ...e switch software to determine what IP address the DHCP software on the switch gave to your device 3 BOOTP DHCP This is a Rockwell Automation tool that lets you assign a specific IP address to a speci...

Страница 3: ...AC address You can download here Need to complete Account Registration https rockwellautomation custhelp com app answers detail a_id 19793 Sysmac Studio Necessary to store software IP address into non...

Страница 4: ...same network ID See two examples below Using Port1 Using Port2 192 168 1 1 DHCP client to be 192 168 1 2 DHCP server 192 168 1 100 192 168 250 1 DHCP client to be 192 168 250 2 DHCP server 192 168 250...

Страница 5: ...Step1 ConfirmMACaddressoftargetunit Confirm the MAC address on the label attached to the back of GI S unit In this case MAC address is 00 00 0A BE 84 AC...

Страница 6: ...000 and power on Wait for the MAC address of target unit to appear in the list NOTE If you don t see the target MAC address in the list possible causes are Wrong rotary DIP switches setting Firewall i...

Страница 7: ...onfigured to 192 168 1 2 but any valid number is available When it s assigned the IP addresses are shown in table above At this point the unit uses the IP address but it s not stored in non volatile m...

Страница 8: ...ct TCP IP Settings Fill the IP address into above box and click Transfer If you see the success message the IP address is stored into non volatile memory The unit works with stored IP address after po...

Страница 9: ...ProcedureforMultipleTargets When IP addresses need to be assigned to multiple target units 8...

Страница 10: ...ting a table for multiple targets in a csv file saves time instead of manually assigning IP address one by one Click File Open and import prepared csv file Configure rotary DIP switches to 000 and pow...

Страница 11: ...ets 3 Enter multicast IP address 2 Select Network Broadcast 4 Click UDP EIP tools searches network and show found targets in right window 5 Click a target The IP address in Station window becomes sele...

Страница 12: ...non volatile memory Execute from 6 to 9 then IP address is stored Repeat from 5 to 9 for all targets 7 Click Get_Attribute_All Confirm Status is OK in green window 8 Select Stored Value 6 Click 0xF5 T...

Страница 13: ...server Network interface of PC is not configured with IP address in same network address Firewall is blocking communication between PC and target device In case error status returns to Set_Attribute...

Страница 14: ...Appendix...

Страница 15: ...ser s manual Z400 E1 section 6 4 1 Setting the IP Address Built in EtherNet IP Port IP Address Settings To obtain the IP address from the DHCP server whenever the power is turned ON instead of using t...

Страница 16: ...nd power on 3 Boot Wireshark tool and start monitoring on Ethernet port 4 Click either of DHCP discover log and click mark 5 MAC address of the unit sent DHCP discover message is shown in Client MAC a...

Страница 17: ...configure the rotary DIP switches to 000 and power on 3 Boot the Wireshark tool and start monitoring the Ethernet port 4 Enter eth src 00 00 0a be 84 ac into filter tool bar 5 Confirm IP address in A...