Step 4: Store IP address
Use Sysmac Studio to store the software IP address to the target unit. In this example,
the safety connection configuration is already complete in the project. Log onto the
PLC and select target unit in Connection Settings, right-click and select “TCP/IP
Settings”. Fill the IP address into above box and click “Transfer”.
If you see the success message, the IP address is stored into non-volatile memory.
The unit works with stored IP address after power cycle.
NOTE:
Refer user’s manual Z400-E1, section 6-4-1 Setting the IP Address -
Built-in EtherNet/IP Port IP Address Settings – IP address setting
procedure - Fixing on the IP address obtained from the DHCP
server when the power is turned ON for detailed procedure.