Low Voltage Switch Gear
Appendix
91
Additional ordering information for contactors
CE-Marking
The manufacturer has to sign his products with the CE-Marking. With
the CE-Marking the manufacturer confirms the accordance with the
different EEC Directives. The CE-Marking is absolutely necessary to
sell the products in the EEC.
Attached you find the EEC Directives concerning our products.
Low Voltage Directive (73/23/EEC)
EMC Directive (89/336/EEC)
Declarations of Conformity art. no. D586.. on request.
Test Authorities, Registration Mark, Approvals
OMRON Low voltage switchgear is built and tested to national and
international specifications. All devices suit all important specifica-
tions without any test obligation, like VDE, BS and also relative to
IEC Recommendations and to European Standards like IEC 947 and
EN 60947.
It is for this reason OMRON Low voltage switchgear is used all over
the world. In order to provide special versions, limitations to the max.
voltages, currents and power ratings or special markings are some-
times necessary.
OMRON Low voltage switchgear is also suitable for applications in
marine environments.
They are classified in "Lloyd`s Register of Shipping" and in the "Mari-
time Register of Shipping" (GUS). The "American Bureau of Ship-
ping" does not claim a general approval for single components, the
complete electrical equipment on board has to be approved. The
devices should have UL- and CSA-approvals. Further information for
Guide-No. and File-No. (CSA, UL) you will find on page 95.
For approved values see technical data of the devices.
State deputy
Explanations for choice and supply of low voltage switchgears in Canada and USA
Marking of auxiliary contacts
At several devices in UL-data are two voltages for auxiliary contacts
mentioned (e. g.: 600 volts at same potential, 150 volts at different
potentials). That means, if the voltage is higher than 150 volts, the con-
trol voltage applied to input terminals must be at the same potential
Low voltage switchgear for auxiliary circuits (e. g. contactor relays,
control units, auxiliary contacts in general) usually approved for
"Heavy Duty" or "Standard Duty" UL and besides these marked with
the admissible max. voltage or with short codes (see table).
Country
Canada
USA
Switzer-
land
Den-
mark
Norway Sweden Finland Poland
Slowa-
kia
Czech
Hun-
garia
State deputy or private
examination
(state admitted)
CSA UL
UL
SEV
DEMKO NEMKO SEMKO SETI
SEP
SKTC
EZU
MEEI
Label marking of ex-
amination boards
*1
Duty of approvals
All switchgear
or
R
Approval of
switchgear
commendable
No approval since 1.1.1994
Our devices are according to the harmonised
European Standards e.g. EN 60947 (IEC 947,
VDE 0660) and can be used generally
Specification
UL is authorised for approvals
acc. to Canadian Standards
Marking with approbation label is no longer
necessary
*1
CSA-approvals are replaced by UL-approvals valid for USA and Canada. From 1. 1. 2000 switchgear will be marked with the combined ap-
proval. UL-mark
or
only.
Marking of
auxiliary
contacts
according to
CSA and UL
Max. rated values per pole
Contact
Rating
Code
Designa-
tion
Voltage
V
Current
Cont.
Current
A
Make
A
Break
A
Heavy Duty
(HD or HVY DTY)
AC 120
60
6
10
A150
AC 240
30
3
10
A300
AC 480
15
1,5
10
A600
AC 600
12
1,2
10
A600
DC 125
2,2
2,2
10
N150
DC 250
1,1
1,1
10
N300
DC 600
0,4
0,4
10
N600
Standard Duty
(SD or STD DTY)
AC 120
30
3
5
B150
AC 240
15
1,5
5
B300
AC 480
7,5
0,75
5
B600
AC 600
6
0,6
5
B600
DC 125
1,1
1,1
5
P150
DC 250
0,55
0,55
5
P300
DC 600
0,2
0,2
5
P600
-
AC 120
15
1,5
2,5
C150
AC 240
7,5
0,75
2,5
C300
AC 480
3,75
0,375
2,5
C600
AC 600
3
0,3
2,5
C600
DC 125
0,55
0,55
2,5
Q150
DC 250
0,27
0,27
2,5
Q300
DC 600
0,1
0,1
2,5
Q600
-
AC 120
3,6
0,6
1
D150
AC 240
1,8
0,3
1
D300
DC 125
0,22
0,22
1
R150
DC 250
0,11
0,11
1
R300
-
AC 120
1,8
0,3
0,5
E150
Marking of
auxiliary
contacts
according to
CSA and UL
Max. rated values per pole
Contact
Rating
Code
Designa-
tion
Voltage
V
Current
Cont.
Current
A
Make
A
Break
A