20
Modular Temperature Controller for Gradient Temperature Control
EJ1G
Mounting to the DIN Rail
Mounting
Catch the hook located on the top of the Unit onto the DIN Rail and
press the Unit until the Unit locks into place.
Dismounting
Pull down on the hook with a flat-blade screwdriver and lift up on the
Unit.
Mount one End Plate to each side of the EJ1C-EDU (PFP-M End
Plates are included with the End Unit).
Install the DIN Rail vertically to the ground.
Applicable DIN Rail (sold separately): PFP-100N (100 cm),
PFP-50N (50 cm)
Wiring Procedure for Screw-less Clamp
Terminals
There are two holes for each terminal. The hole on the right is the
operating hole; the hole on the left is the wire hole. Insert a flat-blade
screwdriver with a width of 2.5 mm into the operating hold and then
insert the wiring into the wire hole. The wire will be clamped when
the screwdriver is removed.
Use crimp terminals for wiring that match the cross-sectional area of
the wiring material.
We recommend the following crimp terminals:
Weidmuller H-sleeve series
Connecting to the G3ZA (EJ1G-TC)
Refer to the
“G3ZA Instruction Manual”
for wiring methods.
(1) Lower the hooks.
(3) Press in
on the
Unit.
(2) Catch the upper hook
onto the DIN Rail.
(4) Make sure the Unit
is locked into place.
Flat-blade Screwdriver
PFP-M
Correct
Incorrect
Vertically
Horizontally
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
SW2
SW1
ERROR
OCC
SD/RD
READY
CN1
Connect the G3ZA
Connecting Cable to
the CN1 connector on
the bottom of the TC
Unit.
G3ZA
CN1
EJ1C-CBLA050 (Order separately)
(cable length: 5m)
Connect the black line with a
white stripe to terminal 7 on the
G3ZA and the black line with no
stripe to terminal 8.
Refer to the following manual for precautionary information and other information necessary to use the EJ1G:
EJ1G Modular Temperature Controller Operation Manual (Cat. No. H143)