WIRING FOR CONFORMANCE TO THE EMC DIRECTIVES
Thermocouple Input Model
Platinum Resistance Thermometer Input Model
Setting display unit
24 VDC
E5ZE
FG
Outside the control panel
Inside the control panel
Ferrite core: ZCAT2032 by TDK
Filter: MBS-1210-22 by Nemic Lambda
I/O terminals
Power supply
Communications cable
Ferrite core
Filter
PLC
or
Alarm output
Control output
CT input
E5ZE-CBL
00
Setting display unit
24 VDC
E5ZE
FG
Outside the control panel
Inside the control panel
I/O terminals
Communications cable
Power supply
PLC
or
Alarm output
Control output
CT input
E5ZE-CBL
00
Platinum resistance
thermometer input
Thermocouple input
Note: 1. Place the power supply, filter, input sensor, I/O terminals, and communications cable inside the control panel when wiring them.
2. If the communications cable between devices extends outside the control panel, satisfy the following conditions when wiring
them.
•
Use shielded cables for communications cables and ground to the FG.
•
Insert at least five ferrite cores close to the E5ZE.