Multipoint Temperature Controller 

E5ZE-8

@D1@B-V2

Input Ranges

Thermocouple

Platinum Resistance Thermometer

Note: 1. A temperature range is factory-set to a range of –200

°

 to

1,300

°

C (for K(CA)) or –100.0

°

 to 500.0

°

C (for Pt 100).

2. Thermocouple W is W/Re5-26 (tungsten rhenium 5, tung-

sten rhenium 26).

Characteristics

Input 

(switch 

selectable)

K (CA)

Chromel 

vs. alumel 

(see 

note 1)

J (IC)

Iron vs. 

constan-

tan

R

Platinum 

vs. Plati-

num rhod-

ium 13%

S

Platinum 

vs. Plati-

num rhod-

ium 10%

T (CC)/U

Copper 

vs. con-

stantan

E (CRC)

Chromel 

vs. con-

stantan

B

Platinum 

rhodium 

30% vs. 

platinum 

rhodium 

6%

N

Nichrosil 

vs. nisil

L

Iron vs. 

constan-

tan

U

Copper 

vs. con-

stantan

W

(see 

note 2)

PL-II

(Platinum)

Range

°

C

–200 to 
1,300

–100 to 
850

0 to 1,700

0 to 1,700

–200 to 
400

0 to 600

100 to 
1,800

0 to 1,300

–100 to 
850

–200 to 
400

0 to 2,300

0 to 1,300

°

F

–300 to 
2,300

–100 to 
1500

0 to 3,000

0 to 3,000

–300 to 
700

0 to 1100

300 to 
3,000

0 to 2,300

–100 to 
1,500

–300 to 
700

32 to 4,100 0 to 2,300

Setting no.

0

1

2

3

4

5

6

7

8

9

A

B

Min. setting 
unit

1

°

C or 0.1

°

C

Input 

(switch selectable)

Pt 100

(see note 1)

JPt 100

Range

°

C

–100.0 to 500.0

–100.0 to 500.0

°

F

–100.0 to 900.0

–100.0 to 900.0

Setting no.

0

1

Min. setting unit

1

°

C or 0.1

°

C

Measurement accuracy (see note)

Thermocouple:

(

±

0.3% of the process value or 

±

2

°

C, whichever greater) 

±

1 digit max.

(

±

0.3% of the process value or 

±

3.6

°

F, whichever greater) 

±

1 digit max.

Platinum resistance thermometer:

(

±

0.3% of the process value or 

±

0.8

°

C, whichever greater) 

±

1 digit max.

(

±

0.3% of the process value or 

±

1.5

°

F, whichever greater) 

±

1 digit max.

Hysteresis

0.0

°

 to 99.9

°

C/

°

F for ON/OFF control only (in units of 0.1

°

C/

°

F)

Cooling coefficient

0.0 to 10.0 (in units of 0.1)

Proportional band

0.0

°

 to 999.9

°

C/

°

F (in units of 0.1

°

C/

°

F)

Cooling side: Cooling coefficient 

×

 Proportional band

Integral (reset) time

0 to 3,999 s (in units of 1 s) (for both heating and cooling)

Derivative (rate) time

0 to 3,999 s (in units of 1 s) (for both heating and cooling)

Control period

Heating side:

1 to 99 s (in units of 1 s)

Cooling side:

1 to 99 s (in units of 1 s)

Sampling period

200 ms for 8 control points

Dead band/overlap band

–999

°

 to 999

°

C/

°

F (in units of 1

°

C/

°

F)

Alarm output setting range

–999

°

 to 9999

°

C/

°

F, 0 to 9999

°

C/

°

F (upper- and lower-limit alarm) (in units of 1

°

C/

°

F)

–999.9

°

 to 9999.9

°

C/

°

F, 0.0 to 9999.9

°

C/

°

F (upper- and lower-limit alarm) (in units of 0.1

°

C/

°

F) (see note 

3)

Fuzzy strength

0% to 99% (in units of 1%)

Fuzzy scale 1

0.2

°

 to 999.9

°

C/

°

F (in units of 0.1

°

C/

°

F)

Fuzzy scale 2

0.02

°

 to 99.99

°

C/s or 

°

F/s (in units of 0.01

°

C/s or 

°

F/s)

Set value backup

Lithium battery

Set value backup period

10 years min. provided that the ambient temperature is within the room temperature

Insulation resistance

20 M

 min. between the FG terminal and all analog input terminals (at 500 VDC)

Dielectric strength

A leakage current of 1 mA AC max. with 500 VAC for 1 minutes between the FG terminal and all analog 
input terminals

Vibration resistance

Malfunction: 10 to 55 Hz, 15 m/s

2

 for 8 min each in X, Y, and Z directions

Destruction: 10 to 55 Hz, 20 m/s

2

 for 8 min each in X, Y, and Z directions

Shock resistance

Malfunction: 150 m/s

2

, 3 times each in 6 directions

Destruction: 200 m/s

2

, 3 times each in 6 directions

Ambient temperature

Operating:

0

°

 to 55

°

C (with no icing or condensation)

Storage:

–25

°

 to 65

°

C (with no icing or condensation)

Ambient humidity

Operating:

35% to 85%

Storage:

35% to 95%

Содержание E5ZE-8 D1 B-V2

Страница 1: ...re inputs Model Number Structure Model Number Legend 1 Number of Control Points 8 8 channels 2 Control Method A Standard heating or cooling V Heating and cooling 3 Control Output Heating Side Q Voltage output for driving SSR C Current output 4 Heater Burnout and SSR Failure Detection See note 1 H Available A Not available 5 Communications Function D1 DeviceNet 6 Input TC Thermocouple P Platinum re...

Страница 2: ... Current Transformers CT Special Cables Recommended Power Supplies No of control points Control method Control output Heater burnout and SSR failure detection Input type Thermocouple Platinum resistance thermometer 8 Standard see note 1 Voltage Available see note 2 E5ZE 8AQHD1TCB V2 E5ZE 8AQHD1PB V2 Current Not available E5ZE 8ACAD1TCB V2 E5ZE 8ACAD1PB V2 Heating and cooling Voltage Available see ...

Страница 3: ...VDC max OFF leakage current 1 mA DC max Alarm outputs Temperature alarm The total output of all control points alarm 1 NPN open collector output and alarm 2 NPN open collector output HB alarm heater burnout detection Total output of all control points 1 point NPN open collector output HS alarm SSR failure detection Total output of all control points 1 point NPN open collector output Temperature co...

Страница 4: ... for ON OFF control only in units of 0 1 C F Cooling coefficient 0 0 to 10 0 in units of 0 1 Proportional band 0 0 to 999 9 C F in units of 0 1 C F Cooling side Cooling coefficient Proportional band Integral reset time 0 to 3 999 s in units of 1 s for both heating and cooling Derivative rate time 0 to 3 999 s in units of 1 s for both heating and cooling Control period Heating side 1 to 99 s in uni...

Страница 5: ...the distance between nodes farthest from each other 3 The maximum network length is 100 m if a thin dedicated cable is applied to the trunk line NOTICE This product has been tested by ODVA s authorized Independent Test Lab and found to comply with ODVA Conformance Test Soft ware Version A 13 For the specifications of objects in details refer to the E5ZE 8 Com munication Manual H114 DeviceNet Commu...

Страница 6: ...le Platinum resistance thermometer E5ZE 8 D1 B V2 E5ZE CBL200 E5ZE CBL200 E5ZE CBL200 XW2D 20G6 Connector Terminal Conversion Unit XW2D 20G6 Connector Terminal Conversion Unit G7TC OC08 G7TC OC16 I O Block G70D V O 16 Relay terminal Host Unit Compatible with Explicit Message Communications OMRON s C200HW DRM21 EV1 CVM1 DRM21 EV1 and CS1W DRM21 Note When replacing with an E5ZE 8 D1 B part of the la...

Страница 7: ... up otherwise operating errors may result Prepare four M4 screws to mount the E5ZE to control panels Use flat washers and spring washers with screws to mount the E5ZE to control panels so that the screws will not loosen The mounting brackets must be attached to the E5ZE with the four M3 6 screws provided with the E5ZE and each of the screws should be tightened to a torque of 0 43 to 0 58 N m or 4 ...

Страница 8: ... CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICATION OR REPAIR Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards codes or regulations that apply to the combination of products in the customer s application or use of the products At t...

Отзывы: