background image

E5EX–H

E5EX–H

3

 Temperature Controller Characteristics

Setting accuracy*

+

0.3% of set value or 

±

1

°

C, whichever 

±

1 digit max.

Set value coincides with the indicated value, because no relative error exists between both values.

Indication accuracy

Hysteresis (during ON/OFF
control action)

0.0

°

 to 999.9 

°

C/

°

F (in units of 0.1

°

)

Proportional band

0.0

°

 to 999.9 

°

C/

°

F (in units of 0.1

°

)

Integral time (Reset time)

0 to 3,999 s (in units of 1 s)

Derivative time (Rate time)

0 to 3,999 s (in units of 1 s)

Alarm output setting range

Thermocouple: –999

°

 to 9,999

°

C/

°

F

Platinum resistance thermometer (Pt100): –99.9

°

 to 999

°

C/

°

F

Control period

Pulse output: 1 to 99 s (in units of 1 s)

Sampling period

500 ms

Output refresh period

Pulse output:

500 ms

Current output: 500 ms

Display refresh period

500 ms

Input shift

Thermocouple: –999

°

 to 9,999

°

C/

°

F

Platinum resistance thermometer (Pt100): –99.9

°

 to 999.9

°

C/

°

F

Insulation resistance

20 M

 min. (at 500 VDC) (measured with a Control Output Unit attached)

Dielectric strength

2,000 VAC 50/60 Hz for 1 minute between terminals of different polarity (measured with a Control
Output Unit attached)

Vibration

Malfunction durability: 2 to 55 Hz, 2G 10 min each in X, Y, and Z directions
Mechanical durability: 10 to 55 Hz, 0.75-mm double amplitude 2 hrs each in X, Y, and Z directions

Shock

Malfunction durability: 100 m/s

2

 3 times each in 6 directions

Mechanical durability: 300 m/s

2

 3 times each in 6 directions

Ambient temperature

Operating: –10

°

 to 55

°

C

Storage:

–25

°

 to 65

°

C

Humidity

35% to 85%

Memory protection

Non-volatile memory

Enclosure ratings

Front panel controls: IEC standard IP50 (dust-proof)
Rear case:

IEC standard IP20

Terminals:

IEC standard IP00

Weight

300 g

*The accuracy of U at temperatures from –150

°

 to 400

°

C (–240

°

C to 700

°

F) is 

±

2

°

C (

±

3.6

°

F) 

±

1 digit. Accuracy is reduced below –150

°

C

(–240

°

F). The accuracy of R and S from 0

°

 to 200

°

C (0

°

 to 400

°

F) is 

±

3

°

C (

±

5.4

°

F) 

±

1 digit.

 Output Unit Characteristics

Relay unit life expectancy

Mechanical: 10,000,000 operations min.

Electrical: 100,000 operations min.

 Current Transformer Characteristics

Max. heater current

50 A, single-phase

Indication accuracy of heater current

±

5% of full scale 

±

1 digit max.

Heater current setting range

0.1 to 49.9 A* (in units of 0.1 A)

Min. detectable ON time

200 ms**

*Heater burnout is not detected when current is set to 0.0 A; the burnout alarm will be automatically turned ON when current is set to 50.0 

**When the control output is ON for less than 200 ms, heater burnout is not detected and heater current is not measured.

Содержание E5EX-H

Страница 1: ...dered by adding F to the end of the model number Example E5EX AH F The scale indication switch will then be set to F prior to shipment from the factory Temperature Controllers Model E5EX AH Control Output Units Output Relay output SSR output Voltage output for driving SSR 12 VDC NPN 24 VDC NPN 24 VDC PNP Model E53 R E53 S E53 Q E53 Q3 E53 Q4 Current Transformers Hole diameter 5 8 mm 12 0 mm Model ...

Страница 2: ...er heights 11 mm and 8 mm Other functions Upper and lower limits for set value Key protection Input shift Display unit selection C F Normal and reverse output selection Watchdog timer function Detects failures in the CPU and restores the CPU Approved standards UL File No E68481 CSA File No LR59623 SEV Control Output Unit Ratings Relay Output Unit E53 R SPDT 5 A 250 VAC resistive load SSR Output Un...

Страница 3: ...G 10 min each in X Y and Z directions Mechanical durability 10 to 55 Hz 0 75 mm double amplitude 2 hrs each in X Y and Z directions Shock Malfunction durability 100 m s2 3 times each in 6 directions Mechanical durability 300 m s2 3 times each in 6 directions Ambient temperature Operating 10 to 55 C Storage 25 to 65 C Humidity 35 to 85 Memory protection Non volatile memory Enclosure ratings Front p...

Страница 4: ...ignated to start auto tuning Press this key for 1 second or more during auto tuning to stop auto tuning Up Key When pressed increases the set temperature or other parameters Successively increases the value when held down Down Key When pressed decreases the set tem perature or other parameters Succes sively decreases the value when held down Display Key Use this key when shifting the dis play to t...

Страница 5: ...down the hook with your finger 2 Connect a Control Output Unit to the vacant socket on one of the printed circuit boards see the figure below A white square is marked on the Control Output Unit Be sure to install the Unit with this marking facing the direction indicated by the arrow in the figure below Mount the Control Output Unit with this mark facing the di rection indicated by the arrow To rem...

Страница 6: ...J 100 to 850 100 to 1 500 4 T 200 to 400 300 to 700 5 E 0 to 600 0 to 1 100 6 JPt100 99 9 to 450 0 99 9 to 800 0 7 Pt100 99 9 to 450 0 99 9 to 800 0 8 L 100 to 850 100 to 1 500 9 U 200 to 400 300 to 700 JPt100 100 C 139 16 Ω JIS Japan Industrial Standard Pt100 100 C 138 5 Ω DIN JIS Operating Mode Selector SW201 FUNCTION This DIP switch selects the operational aspects listed in the follow ing table...

Страница 7: ...ower limit alarm with standby sequence 3 X Platinum resistance thermometer 99 9 to 999 9 8 Event alarm 1 Y 0 9 Proportional alarm pro See Note 2 Note 1 If a negative value is set as X operation will be as follows Lower limit alarm Upper limit alarm Proportional alarm X X X SP SP SP 2 The alarm mode selector can be used to select the proportional alarm mode The proportional alarm function is initia...

Страница 8: ...t PID constants Setting limits control peri od hysteresis heater cur rent heater burnout set ting Control output variable temperature sensor type alarm mode Level 0 In this mode parameters such as the alarm values PID constants and input shift values can be set or changed When these parame ters are being set or changed the new values are displayed on the SV display The parameter to be manipulated ...

Страница 9: ...etting is 60 seconds Input Shift in 5 When pin 3 on the internal operating mode selector DIP switch SW201 is set to the ON position the input shift function can be used This function is used to shift the temperature display from the measured value by a desired value as illustrated by the examples in the following table Input shift value Temperature measured by sensor Displayed temperature 0 withou...

Страница 10: ... in a range from 1 to 99 seconds in units of 1 second The factory setting is 20 seconds When a Voltage Output Unit is used it is recommended that the control period be set to 20 seconds or less ideally about 2 seconds so that the control action can be performed more accu rately Control output ON OFF 20 seconds When control period is set to 20 seconds Heater Burnout Alarm ct hb Set a burnout curren...

Страница 11: ...and heater burnout alarm value can be set or changed Any of these parameters can be selected by pressing dis play key the required number of times as follows Upper limit value of tem perature setting range Lower limit value of temper ature setting range Hysteresis Press a Press a Press a Press a Press a 5l l 5l h hys ct hb Heater current Heater burnout alarm Of the above parameters only the hyster...

Страница 12: ... a range of 0 0 to 100 0 Temperature Sensor in t When in t is displayed on the PV display a message identifying the selected temperature sensor i e the present setting of the tem perature sensor selector SW206 is displayed on the SV display The following table shows the messages that may be displayed Display Sensor r pr R 5 pr S k ca K j ic J t cc T e cr E jpt JPt100 pt Pt100 l ic L u cc U Meets J...

Страница 13: ... cooling operation To stop auto tuning hold down the AT key again for 1 second or more Automatic tuning can be executed at any time on power up while the temperature is rising and after the control ac tion has stabilized Set temperature Old PID constants Limit Cycle Method New PID constants AT indicator blinks AT key is pressed Limit cycle method The optimum PID constants are calculated by this me...

Страница 14: ...not made by turning power off once and on again OFF OFF When the J thermocouple is used however this error message is not displayed until the temperature has risen above the set temperature range by more than 70 C When the temperature resistance thermometer is used this message is displayed when the temperature has fallen to 99 9 C The Temperature Controller displays the following error message in...

Страница 15: ...ust be separated from pow er lines and load lines Use the specified compensating conductors for thermocouples When using a thermocouple as the temperature sensor attach the short circuit bar shown in the terminal block diagram on the hous ing Use lead wires having a small resistance for temperature resis tance thermometers Be sure to remove the short circuit bar from the terminals when a temperatu...

Страница 16: ...n Phone 06 282 2500 Fax 06 282 2749 Telex 522 2484 OMRONO J ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No H49 E1 1 In the interest of product improvement specifications are subject to change without notice Printed in Japan 0590 3M 0590 ...

Отзывы: