E5ED-800/E5ED-B-800
30
External Connections
E5ED-800
Note: 1.
The application of the terminals depends on the model.
2.
Do not wire the terminals that are shown with a gray background.
3.
When complying with EMC standards, the cable that connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
4.
Connect M3 crimped terminals.
5.
Due to UL Listing requirements, use the E54-CT1L or E54-CT3L Current Transformer with the factory wiring (internal wiring).
Use a UL category XOBA or XOBA7 current transformer that is UL Listed for field wiring (external wiring) and not the factory wiring
(internal wiring).
23
24
11
12
19
20
21
22
9
10
2
7
8
17
5
6
3
4
1
13
14
15
16
18
2
1
2
(no polarity)
100 to 240 VAC
1
24 VAC/DC
V
−
23
V
24
+
22
TC
22
+
−
mA
−
+
23
22
23
24
Pt
I
24
22
23
24
+
−
(1) Control output
3
4
5
6
3
4
5
6
RX
R
Q
OUT1
OUT1
A
B
B
QX
21
19
20
17
18
15
16
808
Communications, 2 event
inputs, and 1 CT input
13
14
EV1
EV2
B(+)
A(
−
)
(
−
)
RS-485
CT1
(2) Auxiliary Outputs
7
8
11
12
Auxiliary outputs 1, 2
9
10
Auxiliary output 1
The E5ED-800 is set for a K-type thermocouple (input type = 5) by
default. An input error (
s.err
) will occur if the input type setting does
not agree with the temperature sensor. Check the input type.
Control output 1
Relay output
250 VAC, 5 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 40 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max
(5) Sensor (Temperature/Analog) Input
(6) Options
Models with
1 Relay Output
Models with 1 Voltage
Output (for Driving SSR)
Relay output
250 VAC, 2 A
(resistive load)
Auxiliary outputs 1, 2
E5ED-
@@
2
@
D M
-
@@@
↑
Terminal type
(1) (2) (3) (4) (5)
(6)
(3) Input Power Supply
A
D
Auxiliary output 2
+
−
Models with 1 linear
current Output
3
4
5
6
C
OUT1
CX
804
Communications (RS-485),
2 event inputs
18
13
14
15
16
17
21
19
20
RS-485
EV1
EV2
B(
+
)
A(
−
)
(
−
)