E5CD-800/E5CD-B-800
13
E5CD-B-800 (Push-In Plus Terminal Blocks)
Note: 1.
The application of the terminals depends on the model.
2.
Do not wire the terminals that are shown with a gray
background.
3.
When complying with EMC standards, the cable that
connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC
standards will not be possible.
4.
Refer to
E5
@
D-B (Push-In Plus terminal block types)
on
page 48 for wire specifications and wiring methods.
5.
Common terminals are indicated with
asterisks (*).
You can use the input power supply and
communications common terminals for
crossover wiring.
Controllers given below if you use
crossover wiring for the input power
supply.
100 to 240 VAC Controllers: 16 max.
24 VAC/VDC Controllers: 8 max.
6.
Due to UL Listing requirements, use the E54-CT1L or E54-CT3L
Current Transformer with the factory wiring (internal wiring).
Use a UL category XOBA or XOBA7 current transformer that is UL
Listed for field wiring (external wiring) and not the factory wiring
(internal wiring).
Isolation/Insulation Block Diagrams
E5CD-B
E5CD-B-800
23
19
22
1
2
17
18
3
15
24
16
6
8
9
14
21
5
13
20
4
12
11
10
7
(2) Auxiliary Outputs
Auxiliary output 2
Auxiliary output 1
804
Communications (RS-485),
Event Inputs 3 and 4
802
Communications
(RS-485), CT1
(
−
)
(
−
)
EV4
EV3
CT1
B(+)
A(
−
)
RS-485
B(+)
A(
−
)
RS-485
13
14
15
16
9
10
11
12
*
*
*
13
14
15
16
*
*
*
*
*
*
*
8
6
7
8
Pt
A
B
B
+
−
mA
−
+
7
6
V
−
V
+
TC
I
6
7
8
6
7
8
17
18
19
20
21
22
23
24
17
18
19
20
21
22
23
24
Use non-voltage inputs for the event
inputs.
The polarity for a non-contact input
is indicated by “(
-
).”
Relay output
250 VAC, 3 A (resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max
Relay outputs
250 VAC, 2 A (resistive load)
Control output 1
Auxiliary outputs 1, 2
The E5CD-B is set for a K-type thermocouple (input type = 5) by
default. An input error (
s.err
) will occur if the input type setting does
not agree with the temperature sensor. Check the input type.
E5CD-
@@
2
@
B M
-
@@@
↑
Terminal type
(1) (2) (3) (4) (5)
(6)
Models with
1 Relay Output
(1) Control output 1
Models with 1
Voltage Output
(for Driving SSR)
OUT1
R
1
2
RX
1
2
OUT1
Q
QX
+
−
Models with 1
Linear Current Output
1
2
OUT1
C
CX
+
−
(5) Sensor (Temperature/Analog) Input
(3) Input Power Supply
100 to 240 VAC
24 VAC/DC
(no polarity)
(6) Options
Wiring Example:
To another E5CD-B
13
14
15
16
Sensor input and CT input
Communications
Relay output
Auxiliary output 1
: Reinforced insulation
: Functional isolation
Power
supply
Auxiliary output 2
Voltage output (for driving SSR) and
linear current output
Sensor input and CT input
Communications and event inputs
Voltage output (for driving SSR) and
linear current output
Relay output
Auxiliary output 1, 2
: Reinforced insulation
: Functional isolation
Power
supply
Содержание E5CD-B-800 Series
Страница 38: ...MEMO 38 ...
Страница 54: ...MEMO 54 ...