background image

E5AX-P

E5AX-P

7

 Motor Calibration: 

calb

The following setting are used to set the opening/closing time for controlling valves. Always set the following parameters when installing the
controller. If a display is required for valve position, set the open and close positions at the same time.

–200

sl–l

calb

fr–l

fr–l

mot

30

Press 

a

.

Press 

a

.

Press 

a

.

Press 

a

.

Press the UP and Down
keys simultaneously.

Lower setting limit

Motor calibration display

Count value

Count value

Fully open position

Fully close position

Fully open/close time

PV

SV

a

Settings when Not Using a Potentiometer (No Valve Position
Display)

1. Turn on power and press the Level Key for at least two

seconds. 

sl–l

 will be displayed. Then press the Display Key

until 

calb

 is displayed.

This is the initial mode when power is turned on for the first
time.

2. Simultaneously press the Up and Down Keys for at least one

second. 

fr–h

 will be displayed and the OPEN output will turn

ON.

3. Press the Display Key. 

fr–l

 will be displayed, the OPEN output

will turn OFF, and the CLOSE output will turn ON.

4. Press the Display Key. 

mot

 will be displayed and the CLOSE

output will turn OFF. While 

mot

 is displayed, use the Up and

Down Keys to set the fully open/close time to a value between
1 and 999 s in the units of 1 s.

5. Press the Display Key. 

sl–l

 will be displayed and motor

calibration will be complete. Press the Level Key for at least
two seconds, confirm that 

in–t

 is displayed, and then press

the Level Key again for at least two seconds to display the
process value and return to the initial display mode.

Settings with a Potentiometer (with Valve Position Display)

1. Turn on power and press the Level Key for at least two

seconds. 

sl–l

 will be displayed. Then press the Display Key

until 

calb

 is displayed.

This is the initial mode when power is turned on for the first
time.

2. Simultaneously press the Up and Down Keys for at least one

second. 

fr–h

 will be displayed, the OPEN output will turn ON,

and the valve will start to open. Press the Display Key as soon
as the valve stops by the limit switch built into the motor. The
count value for the fully open position will be set.

3. Press the Display Key. 

fr–l

 will be displayed, the OPEN output

will turn OFF, the CLOSE output will turn ON, and the valve
will start to close. Press the Display Key as soon as the valve
stops by the limit switch built into the motor. The count value
for the fully close position will be set.

4. Press the Display Key. 

mot

 will be displayed and the CLOSE

output will turn OFF. The automatically set fully open/close
time will be displayed. Use the Up and Down Keys to adjust
the setting if required (value must be between 1 and 999 s in
the units of 1 s).

5. Press the Display Key. 

sl–l

 will be displayed and motor

calibration will be complete. Press the Level Key for at least
two seconds, confirm that 

in–t

 is displayed, and then press

the Level Key again for at least two seconds to display the
process value and return to the initial display mode.

WARNING

Never calibrate the motor during control operation. Make sure
that control operations have been stopped before calibrating.

Note:

1. The output mode cannot be changed in motor calibra-

tion mode.

2. If the fully open position is less than the fully closed posi-

tion, the value position will not be displayed and the dis-
play will show “

a––– 

” for automatic and “

m––– 

” for manu-

al operation. If a potentiometer is not being used for
feedback, press the Display Key at steps 2 and 3 without
regarding the position of the valve and then set the fully
open/close time. Here too, the display for value position
will show “

a––– 

” for automatic and “

m––– 

” for manual

operation.

Содержание E5AX-P Series

Страница 1: ...ct communications Specify a terminal block by adding X to the model number Example E5AX PRR02 X Capable of transmitting the process value or output value but remote setting by external input is not possible Temperature Ranges Input switch selectable Thermocouple Temperature resistance thermometer K Chromel vs alumel J L Iron vs constantan T U Copper vs constantan E Chromel vs constantan R Platinum...

Страница 2: ...ration function Watchdog timer function Detects failures in the CPU and restores the CPU Manual output balanceless bumpless operation switchable Communications Protocol RS 232C RS 422 RS 485 BCD Transmission output Transmission method Half duplex Data select code 4 to 20 mA DC Load 600 W max Resolution Approx 3 200 Synchronization method Start stop synchronization Baud rate 150 300 600 1 200 2 400...

Страница 3: ...Platinum resistance thermometer 99 9 to 999 9 C F in units of 0 1 C F Insulation resistance 20 MW min at 500 VDC Dielectric strength 2 000 VAC 50 60 Hz for 1 min between terminals of different polarities Vibration resistance Malfunction 2 to 55 Hz 2G 10 min each in X Y and Z directions Destruction 10 to 55 Hz 0 75 mm double amplitude 2 hrs each in X Y and Z directions Shock resistance Malfunction ...

Страница 4: ...reases the value when held down Front Cover Close Output Indicator Lights when the close out put is ON Operation NOTICE Always turn off the power supply to the Electronic Temperature Controller before changing any switch settings Settings 1 Remove the internal mechanism from the housing Lift the internal mechanism while pressing the hook at the bottom of the front panel Hook Pull out the internal ...

Страница 5: ... protection cancel is effective only when SW101 key protec tion is on If the SP protection cancel is ON key protection SW101 ON will not apply to the set point i e you will be able to change the set point regardless of the setting of SW101 Alarm Mode Selector SW205 ALM Alarm mode selector is provided on all E5AX Temperature Controllers Alarm modes listed in the following table can be selected usin...

Страница 6: ... position the Level Key Up and Down Keys and Auto tuning Key cannot be operated In effect the Temperature Controller is write protected and the set values such as the alarm value can be read out only The set point however will not be protected if the SP protection disable is turned ON pin 4 of SW201 ...

Страница 7: ...en press the Display Key until calb is displayed This is the initial mode when power is turned on for the first time 2 Simultaneously press the Up and Down Keys for at least one second fr h will be displayed the OPEN output will turn ON and the valve will start to open Press the Display Key as soon as the valve stops by the limit switch built into the motor The count value for the fully open posit...

Страница 8: ...t displayed when the alarm is disabled SW203 set to 0 or 9 4 Not displayed when the input shift display is disabled SW201 pin 3 OFF 5 Not displayed when PID display is disabled SW201 pin 6 OFF Main Setting The set point can be changed with the Up and Down Keys Valve Travel The value travel can be monitored If a potentiometer is not con nected the display will show a for automatic and m for manual ...

Страница 9: ...d using the Up and Down Keys The new value will be displayed on the SV display It can be set in a range from 0 1 to 999 9 C F in units of 0 1 C F The factory setting is 40 0 C F NOTICE The output value will change according to the differ ence between the set value and the present value when the proportional band is changed during control operation If this difference is too great a drastic change w...

Страница 10: ...er calibrate the motor during control operation Make sure that control operations have been stopped before calibrating fr h Fully open position fr l Fully closed position mot Opening closing time The motor is calibrated Refer to page 9 Level 2 In level 2 selected input sensor and modes for alarm output can be monitored Note that level 2 is a monitoring level only and thus no parameters can be chan...

Страница 11: ...own the Level Key and Mode Key again simultaneously for 1 second minimum All settings will re turn to those prior to the beginning of auto tuning Automatic tuning can be executed at any time at power application while the temper ature is rising or after the control action has stabilized Error Messages The Temperature Controller is provided with self diagnostic functions and will display an error m...

Страница 12: ...N Controllers 92 0 8 0 92 0 8 0 92 0 8 0 120 min L L 96N 3 5 1 0 _96 89 Mounting Screw 12 11 5 2 to 10 SG Installation Note 1 Connect a valve position indicator if required 2 Do not connect unused terminals Control output Open Close Alarm output Potentiometer input see Note 1 100 to 240 VAC 50 60 Hz Ground FG terminal 18 under noise interfered environment Use these terminals when connecting a plat...

Страница 13: ...ce because do ing so may damage them The terminal block of the Temperature Controller is constructed so that the lead wires can be connected to all the terminals from the same direction Top Bottom Input Connection To reduce inductive noise influence the lead wires connecting the input to the Temperature Controller must be separated from the power lines and load lines Use the specified compensating...

Страница 14: ...saka 540 Japan Phone 06 949 6070 Fax 06 949 6084 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No H54 E1 1A In the interest of product improvement specifications are subject to change without notice Printed in Japan 0791 1M ...

Отзывы: