E5AX-LA/-MA
E5AX-LA/-MA
5
Operation
NOTICE:
Always turn off power to the Digital Controller before changing any switch settings.
Settings
1. Remove the internal mechanism from the housing. Lift the
internal mechanism while pressing the hook at the bottom of
the front panel.
Hook
Pull out the internal mechanism
while holding down the hook with
your finger.
2. Connect a Control Output Unit to the vacant socket on the
printed circuit board as shown below.
Mount the Control Output Unit
with this mark facing the direction
indicated by the arrow.
Set the output selector to PUL (Pulse) when a Relay
(SW202, OUT), SSR, or Voltage Output Unit is mounted.
Set the output selector to CUR (current) when a Current
Output Unit is mounted.
To remove a Control Output Unit, push it up with the tip of
a flat-blade screwdriver as shown below.
Flat-blade screwdriver
Output Selector (SW202)
PUL
CUR
OFF
ON
Output
Setting
(factory-set to OFF)
Current
ON
Pulse
OFF
3. Four internal switches must be set on the E5AX: the input
type selector, the operating mode selector, and the alarm
mode selectors 1 and 2.
The figures show the locations of these switches and the
protection switches on the internal mechanisms. The
protection switch can be used to disable key operation.
Protection switch (SW101, PROTECT)
Alarm mode selector 2
(SW203, ALM2)
Operating mode selector (SW 201,
FUNCTION)
Alarm mode selector 1
(SW205, ALM1)
Input type selector (SW206,
INPUT)
Output selector
(SW202, OUT)