E5AX-LA/-MA

E5AX-LA/-MA

2

Specifications

 

Digital Controller Ratings

Supply voltage

100 to 240 VAC, 50/60 Hz (either frequency applicable with same unit)

Operating voltage range

85% to 110% of rated supply voltage

Power consumption

Approx. 10 VA (at 100 VAC) to 15 VA (at 240 VAC)
Approx. 12 VA (at 100 VAC) to 15 VA (at 240 VAC) with communication function

Input

E5AX-LA: 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 1 V
E5AX-MA: 0 to 100 mV, 0 to 10 mV, –10 to 10 mV

Input impedance

Current input: 150 

W

Voltage input: 1 M

W

 min.

Control output

See 

Control Output Unit Ratings.

Control mode

ON/OFF or PID control with auto-tuning

Alarm output

Relay output, 2 independent SPST-NO contacts; 3 A, 250 VAC

Setting method

Digital setting via Up and Down Keys

Indication method

Digital indications (character heights PV: 15 mm and SV: 11 mm) (Color PV: red, SV: green)

Shift set input

No voltage, contact signal input (set value shifted when ON); Contact impedance: 100 

W

 max.

Other functions

Upper and lower limits for set value
Key protection
Input shift
Manual output (balanceless-bumpless operation switchable)
Normal and reverse output selection
Shift set
Scaling
Watchdog timer function (Detects failures in the CPU and restores the CPU.)

Note:

The control output is optically insulated from the internal circuits.

 Control Output Unit Ratings

Relay Output Unit

E53-R

SPDT; 5 A, 250 VAC (resistive load)

SSR Output Unit

E53-S

SPST-NO; 1 A, 75 to 250 VAC (resistive load)
(Leakage current is 1.5 mA max. at 200 VAC)

Voltage Output Unit

E53-Q

40 mA, 12 VDC; NPN (with short-circuit protection)

(for driving SSR)

E53-Q3

20 mA, 24 VDC; NPN (with short-circuit protection)

E53-Q4

20 mA, 24 VDC; PNP (with short-circuit protection)

Current Output Unit

E53-C

4 to 20 mA, DC; Load: 600 

W

 max. resolution: 212

Содержание E5AX-LA

Страница 1: ...equipped with a terminal block to connect communications Specify a terminal block by adding X to the model number Example E5AX LA02 X Capable of transmitting the process value or output value but remo...

Страница 2: ...ons character heights PV 15 mm and SV 11 mm Color PV red SV green Shift set input No voltage contact signal input set value shifted when ON Contact impedance 100 W max Other functions Upper and lower...

Страница 3: ...0 ms Shift set 999 to 9999 Decimal point is displayed at set position Input shift 999 to 9999 Decimal point is displayed at set position Insulation resistance 20 MW min at 500 VDC Dielectric strength...

Страница 4: ...e connected to one host computer using serial communications RS 422 RS 485 3 Outputs process value within the set limits Nomenclature Process Value PV Display Displays not only the process value but a...

Страница 5: ...Output Unit is mounted Set the output selector to CUR current when a Current Output Unit is mounted To remove a Control Output Unit push it up with the tip of a flat blade screwdriver as shown below F...

Страница 6: ...tion Pin number Pin setting Control setting Control mode 1 ON ON OFF operation OFF PID operation Control output 2 ON Normal OFF Reverse Input shift 3 ON Enabled OFF Disabled SP set point 4 ON Enabled...

Страница 7: ...imit of a proportional band When the temperature rises to the upper limit of the proportional band point B in the figure the alarm output is turned ON This alarm function is convenient when the main s...

Страница 8: ...disabled SW201 pin 6 ON Proportional Band p When the character p is displayed on the PV display the propor tional band P constant can be changed using the Up and Down Keys The new value will be displ...

Страница 9: ...t shift 10 0 10 0 1 0 shifted by 1 0 10 0 11 0 1 0 shifted by 1 0 10 0 9 0 This function can be used mainly for fine tuning compensation while leaving the set value unaffected Select this function by...

Страница 10: ...2 seconds so that the control operation can be performed more accurately Control output ON OFF 20 seconds When control period is set to 20 seconds Hysteresis hys The hysteresis value for the ON OFF co...

Страница 11: ...ant control operations to be performed while setting parameters turn off the power and then turn it back on after setting the desired parameters Auto tuning When the Level Key and Mode Key are pressed...

Страница 12: ...ed the input range OFF Approx 1 mA The output will turn ON ac cording to the alarm mode when the input goes to maximum except in the proportional alarm mode in which it will remain OFF e111 flashes e3...

Страница 13: ...ons connector RS 232C and BCD connector is shown Communications board RS 422 and 485 terminals are shown Communications board 4 to 20 mA transmission output is shown 4 to 20 mA transmission output RS...

Страница 14: ...ipment may prevent proper operation Attach the two mounting brackets supplied with E5AX on the top and bottom of the Digital Controller Tighten the screws of the mounting brackets with your fingers Mo...

Страница 15: ...C are supplied with the Digital Controller Attach the proper stickers to the front panel as shown below allowing the input type and Control Output Unit mounted in the Digital Controller to be easi ly...

Отзывы: