manualshive.com logo in svg
background image

Advanced Digital Temperature Controller

 E5

@

N/E5

@

N-H

23

11.

When executing self-tuning, turn ON power to the load (e.g., 

heater) at the same time as or before supplying power to the 
product. If power is turned ON to the product before turning ON 
power to the load, self-tuning will not be performed properly and 
optimum control will not be achieved.

12.

A switch or circuit breaker must be provided close to the product. 

The switch or circuit breaker must be within easy reach of the 
operator, and must be marked as a disconnecting means for this 
unit.

13.

Always turn OFF the power supply before pulling out the interior of 

the product, and never touch nor apply shock to the terminals or 
electronic components. When inserting the interior of the product, 
do not allow the electronic components to touch the case.

14.

Do not use paint thinner or similar chemical to clean with. Use 

standard grade alcohol.

15.

Design the system (e.g., control panel) considering the 2 seconds 

of delay that the product's output to be set after power ON.

16.

The output may turn OFF when shifting to certain levels. Take this 

into consideration when performing control.

17.

The number of EEPROM write operations is limited. Therefore, 

use RAM write mode when frequently overwriting data during 
communications or other operations.

18.

Always touch a grounded piece of metal before touching the 

Temperature Controller to discharge static electricity from your 
body.

19.

Do not remove the terminal block. Doing so may result in failure or 

malfunction.

20.

Control outputs (for driving SSR) that are voltage outputs are not 

isolated from the internal circuits. When using a grounded 
thermocouple, do not connect any of the control output terminals 
to ground. (Doing so may result in an unwanted circuit path, 
causing error in the measured temperature.)

21.

When replacing the body of the Temperature Controller, check the 

condition of the terminals. If corroded terminals are used, contact 
failure in the terminals may cause the temperature inside the 
Temperature Controller to increase, possibly resulting in fire. If the 
terminals are corroded, replace the case as well.

22.

Use suitable tools when taking the Temperature Controller apart 

for disposal. Sharp parts inside the Temperature Controller may 
cause injury.

23.

Before connecting an Output Unit, confirm the specifications and 

thoroughly read relevant information in the datasheet and manual 
for the Temperature Controller.

24.

Check the orientation of the connectors on the Conversion Cable 

before connecting the Conversion Cable. Do not force a 
connector if it does not connect smoothly. Using excessive force 
may damage the connector.

25.

Do not place heavy object on the Conversion Cable, bend the 

cable past its natural bending radius, or pull on the cable with 
undue force.

26.

Do not connect or disconnect the Conversion Cable while 

communications are in progress. Product faults or malfunction 
may occur.

27.

Make sure that the Conversion Cable's metal components are not 

touching the external power terminals.

28.

Do not touch the connectors on the Conversion Cable with wet 

hands. Electrical shock may result.

29.

Before using infrared communications, correctly attach the 

enclosed Mounting Adapter to the cable for the Support Software. 
When connecting the infrared port on the cable to the Support 
Software into the Adapter, insert the connector to the specified 
line. Communications may not be possible if the connector is not 
connected properly.

Precautions for Correct Use 

Service Life 

1.

Use the product within the following temperature and humidity 
ranges:
Temperature: 

10 to 55

°

C (with no icing or condensation)

Humidity: 25% to 85%
If the product is installed inside a control board, the ambient 
temperature must be kept to under 55

°

C, including the temperature 

around the product. 

2.

The service life of electronic devices like Temperature Controllers 
is determined not only by the number of times the relay is switched 
but also by the service life of internal electronic components. 
Component service life is affected by the ambient temperature: the 
higher the temperature, the shorter the service life and, the lower 

the temperature, the longer the service life. Therefore, the service 
life can be extended by lowering the temperature of the 
Temperature Controller. 

3.

When two or more Temperature Controllers are mounted 
horizontally close to each other or vertically next to one another, 
the internal temperature will increase due to heat radiated by the 
Temperature Controllers and the service life will decrease. In such 
a case, use forced cooling by fans or other means of air ventilation 
to cool down the Temperature Controllers. When providing forced 
cooling, however, be careful not to cool down the terminals 
sections alone to avoid measurement errors.

Measurement Accuracy 

1.

When extending or connecting the thermocouple lead wire, be sure 
to use compensating wires that match the thermocouple types. 

2.

When extending or connecting the lead wire of the platinum 
resistance thermometer, be sure to use wires that have low 
resistance and keep the resistance of the three lead wires the 
same. 

3.

Mount the product so that it is horizontally level. 

4.

If the measurement accuracy is low, check to see if input shift has 
been set correctly. 

Waterproofing

The degree of protection is as shown below. Sections without any 
specification on their degree of protection or those with IP

@

0 are not 

waterproof.

Front panel: IP66
Rear case: IP20, Terminal section: IP00
(E5CN-U: Front panel: IP50, rear case: IP20, terminals: IP00)

Operating Precautions

1.

It takes approximately two seconds for the outputs to turn ON from 
after the power supply is turned ON. Due consideration must be 
given to this time when incorporating Temperature Controllers in a 
sequence circuit. 

2.

When using self-tuning, turn ON power for the load (e.g., heater) 

at the same time as or before supplying power to the Temperature 
Controller. If power is turned ON for the Temperature Controller 
before turning ON power for the load, self-tuning will not be 
performed properly and optimum control will not be achieved. 

3.

When starting operation after the Temperature Controller has 

warmed up, turn OFF the power and then turn it ON again at the 
same time as turning ON power for the load. (Instead of turning 
the Temperature Controller OFF and ON again, switching from 
STOP mode to RUN mode can also be used.) 

4.

Avoid using the Controller in places near a radio, television set, or 

wireless installing. These devices can cause radio disturbances 
which adversely affect the performance of the Controller.

Others

1.

The disk that is included with the Conversion Cable is designed for 
a computer CD-ROM driver. Never attempt to play the disk in a 
general-purpose audio player.

2.

Do not connect or disconnect the Conversion Cable connector 
repeatedly over a short period of time. The computer may 
malfunction.

3.

After connecting the Conversion Cable to the computer, check the 
COM port number before starting communications. The computer 
requires time to recognize the cable connection. This delay does 
not indicate failure.

4.

Do not connect the Conversion Cable through a USB hub. Doing 
so may damage the Conversion Cable.

5.

Do not use an extension cable to extend the Conversion Cable 
length when connecting to the computer. Doing so may damage 
the Conversion Cable.

6.

The E5AN-H/E5EN-H use the same port for communications 
through the infrared port and the Support Software port. Do not 
attempt to use communications through the Support Software port 
when the infrared port is being used. 

Содержание E5AN-H

Страница 1: ...ON OFF Counter Model available with position proportional control Main I O Functions 96 96 mm E5AN H 48 96 mm E5EN H Refer to Safety Precautions on page 22 Auto manual switching Temperature Controller status display Simple program function Logic operations Control output ON OFF count alarm PV change rate alarm Models optional with RS 485 or RS 232C communications Event Inputs None Two Four Univers...

Страница 2: ...C 10 Terminal Cover 500 With Terminal Cover Note Casing color is black White Silver available on request Option Units 1 Function EN01 RS 232C communications EN02 RS 422 communications EN03 RS 485 communications AKB Event input Output Units 1 Function RN relay QN pulse PNP 12 VDC Q3 pulse NPN 12 VDC Q4 pulse PNP 24 VDC C3N linear 4 to 20 mA C3DN linear 0 to 20 mA V34N linear 0 to 10 V V35N linear 0...

Страница 3: ...SR output fitted 3 phase 2 4 to 20 mA output 4 to 20 mA input E5AN HSS2HHBFM 500 3 none fitted 2 slots 2 4 to 20 mA output 4 to 20 mA input E5AN HAA3BFM 500 2 SSR output fitted 2 4 to 20 mA output 4 to 20 mA input E5AN HSS3BFM 500 Valve 2 2 relay output fitted 2 4 to 20 mA input E5AN HPRR2BM 500 2 relay output fitted 2 4 to 20 mA output 4 to 20 mA input E5AN HPRR2BFM 500 24 VAC VDC Basic 2 none fi...

Страница 4: ...mA input E5EN HAA2HHBFM 500 2 SSR output fitted 3 phase 2 4 to 20 mA output 4 to 20 mA input E5EN HSS2HHBFM 500 3 none fitted 2 slots 2 4 to 20 mA output 4 to 20 mA input E5EN HAA3BFM 500 2 SSR output fitted 2 4 to 20 mA output 4 to 20 mA input E5EN HSS3BFM 500 Valve 2 2 relay output fitted 2 4 to 20 mA input E5EN HPRR2BM 500 2 relay output fitted 2 4 to 20 mA output 4 to 20 mA input E5EN HPRR2BFM...

Страница 5: ...or D A or B or C or D A and B and C and D A B C and D are four inputs Delay ON delay or OFF delay for the results of the logic operation given above Setting time 0 to 9999 s or 0 to 9999 min Output inversion Possible Output One work bit per operation Work bit assignment Any of The following can be assigned to up to eight work bits logic operation results Event input operations auxiliary outputs or...

Страница 6: ...00 01700 0 1300 0 1300 0 1300 0 850 0 850 0 850 0 600 0 500 0 500 0 500 0 400 0 400 0 400 0 400 0 400 0 200 00 200 00 200 00 200 00 100 0 100 0 100 0 0 0 0 0 0 0 0 0 0 0 0 0 50 00 20 0 50 00 100 0 20 0 50 00 50 00 100 0 200 0 199 9 199 9 200 0 200 0 199 9 200 0 200 0 199 9 200 0 Setting number 0 1 2 24 3 4 5 6 21 7 8 22 9 10 23 11 12 13 14 15 16 17 18 19 20 25 26 27 28 29 Shaded settings are the d...

Страница 7: ...ue 5 Upper and lower limit with standby sequence Always OFF when the upper limit and lower limit hysteresis overlaps 6 Displayed when there is a remote SP input Set val ue Alarm type Alarm output operation When X is positive When X is negative 0 Alarm function OFF Output OFF 1 1 Upper and lower limit 2 2 Upper limit 3 Lower limit 4 1 Upper and lower limit range 3 5 1 Upper and lower limit with sta...

Страница 8: ... 9 FS in units of 0 1 FS Integral time I 0 0 to 3240 0 s in units of 0 1 s Derivative time D 0 0 to 3240 0 s in units of 0 1 s Control period 0 5 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in units of 0 1 Alarm setting range 19999 to 32400 decimal point position depends on input type Affect of signal source resistance Thermocouple 0 1 C Ω max 100 Ω max Platinum resistance thermomete...

Страница 9: ...o condensation or icing Storage humidity 10 to 80 Altitude 2 000 m max Weight Approx 100 g Transmission line connection method RS 485 RS 422 Multipoint RS 232C Point to point Communications RS 485 two wire half duplex RS 422 four wire half duplex or RS 232C Synchronization method Start stop synchronization Protocol CompoWay F SYSWAY or Modbus Baud rate 1200 2400 4800 9600 19200 38400 or 57600 bps ...

Страница 10: ...within the derating curve 2 There is no zero cross function Derating Curve for SSR Outputs Reference Values Condition A SSR outputs 100 ON Condition B SSR outputs 50 ON with 2 s control cycle 500 300 100 50 30 10 5 3 1 0 1 2 3 4 5 6 E5AN H E5EN H 250 VAC 30 VDC resistive load cosφ 1 Switching current A Life 10 4 operations 1 5 1 25 1 0 75 0 5 0 25 0 10 0 10 20 30 40 50 55 45 60 Ambient temperature...

Страница 11: ...3 4 5 6 7 8 9 10 21 22 23 24 25 26 27 28 29 30 21 22 23 24 25 26 27 28 29 30 11 12 13 14 15 16 17 18 19 20 4 to 20 mA DC Load 600 Ω max 4 to 20 mA DC 21 22 23 24 25 26 27 28 29 30 EV4 EV3 Transfer output Remote SP input DON T USE 100 to 240 VAC 24 VAC VDC no polarity Input power supply Auxiliary output 2 Control output 1 Control output 2 CT2 CT1 CT2 DON T USE DON T USE Auxiliary output 1 Control o...

Страница 12: ...ry Crimp terminal size M3 5 96 96 112 91 79 2 6 2 92 0 8 0 92 0 8 0 92 0 8 0 96 number of units 3 5 1 0 0 120 min Group mounting does not allow waterproofing Mounted Separately Group Mounted Recommended panel thickness is 1 to 8 mm Group mounting is not possible in the vertical direction Maintain the specified mounting space between Controllers To mount the Controller so that it is waterproof inse...

Страница 13: ... panel thickness is 1 to 8 mm Group mounting is not possible in the vertical direction Maintain the specified mounting space between Controllers When two or more Controllers are mounted make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications Group mounting is not possible if an SSR output is used for control output 1 or 2 and t...

Страница 14: ... SD USB Infrared Conversion Cable E58 CIFIR USB Infrared Conversion Cable 16 99 2 18 5 23 1 75 21 8 39 Mounting Adapter Accessory With Mounting Adapter Connected Mounting Adapter 2 100 250 1 765 USB connector type A plug Serial connector LED indicator RD LED indicator SD USB Serial Conversion Cable E58 CIFQ1 Terminal Covers E53 COV16 Six Covers provided 10 1 2 3 2 44 8 ...

Страница 15: ...of structure is not required Y92S P5 for DIN 48 96 E54 CT3 Accessory Armature 30 21 15 5 8 dia 25 3 40 10 5 2 8 7 5 10 Two 3 5 dia 40 40 30 12 dia 9 2 36 dia 15 30 Two M3 depth 4 Approx 3 dia 18 22 Approx 6 dia Plug Armature Lead E54 CT1 E54 CT3 Connection Example Plug E54 CT1 Thru current Io vs Output Voltage Eo Reference Values Maximum continuous heater current 50 A 50 60 Hz Number of windings 4...

Страница 16: ...16 Advanced Digital Temperature Controller E5AN H E5EN H ...

Страница 17: ...OFF then back ON again If the display remains the same the controller must be repaired If the display is restored to normal then a probable cause can be external noise affecting the control system Check for external noise OFF OFF e111 E111 Memory error Turn the power OFF then back ON again If the display remains the same the controller must be repaired If the display is restored to normal then a p...

Страница 18: ...Setting Level Adjustment Level Protect Level Monitor Setting Item Level PID Setting Level Bank Setting Level Bank Setting Level Press the O Key less than 1 s Press the O Key less than 1 s Press the O Key less than 1 s PID2 PID3 PID8 PID 8 Integral Time PID 8 Derivative Time PID 8 MV Upper Limit PID 8 MV Lower Limit PID 8 Automatic Selection Range Upper Limit PID 8 Cooling Coefficient PID 8 LBA Det...

Страница 19: ...n of P or PD control Hysteresis Heating Hysteresis Cooling Hysteresis settings Soak Time Wait Band MV at Stop MV at PV Error SP Ramp Set Value MV Upper Limit MV Lower Limit MV Change Rate Limit Process Value Added when Additional PV display is ON Process Value Set Point Auto Manual Switch PID control only Added when auto manual select addition is ON Set Point During SP Ramp Heater Current 1 Value ...

Страница 20: ...Key Protect Restricts PF key operation E5AN H E5EN H only Parameter Mask Enable Displayed only when a parameter mask is set Protocol Setting Switches between CompoWay F SYSWAY and Modbus Communications Unit No Communications Baud Rate CompoWay F SYSWAY only Communications Data Length Communications Stop Bits Communications Parity Send Data Wait Time Press the O Key for at least 1 s Press the O Key...

Страница 21: ...n Compensation Method MB Command Logic Switching PV Change Color PV Stable Band Alarm 1 ON Delay Alarm 2 ON Delay Alarm 3 ON Delay Alarm 1 OFF Delay Alarm 2 OFF Delay Alarm 3 OFF Delay Input Shift Type MV at Stop and Error Addition Auto Manual Select Addition HS Alarm Use HS Alarm Latch HS Alarm Hysteresis LBA Detection Time LBA Level LBA Band Control Output 1 Assignment Control Output 2 Assignmen...

Страница 22: ...s to ensure the correct temperature display Do not touch the terminals while power is being supplied Doing so may occasionally result in minor injury due to electric shock Do not allow pieces of metal wire clippings or fine metallic shavings or filings from installation to enter the product Doing so may occasionally result in electric shock fire or malfunction Do not use the product where subject ...

Страница 23: ...ed inside a control board the ambient temperature must be kept to under 55 C including the temperature around the product 2 The service life of electronic devices like Temperature Controllers is determined not only by the number of times the relay is switched but also by the service life of internal electronic components Component service life is affected by the ambient temperature the higher the ...

Страница 24: ... rear case two on the top and two on the bottom and use it to pry and pull out the front panel slightly Then pull out on the front panel gripping both sides Be sure not to impose excessive force on the panel 3 When inserting the body of the Temperature Controller into the case make sure the PCBs are parallel to each other make sure that the sealing rubber is in place and press the E5AN E5EN toward...

Страница 25: ...Advanced Digital Temperature Controller E5 N E5 N H 25 ...

Страница 26: ...formity with any standards codes or regulations that apply to the combination of products in the customer s application or use of the products Take all necessary steps to determine the suitability of the product for the systems machines and equipment with which it will be used Know and observe all prohibitions of use applicable to this product NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SE...

Отзывы: