manualshive.com logo in svg
background image

2

Inductive Sensors

Rating/Performance

Item

Model

E2FQ-X2

@

E2FQ-X5

@

E2FQ-X10

@

Sensing distance

2 mm ±10%

5 mm ±10%

10 mm ±10%

Setting distance

0 to 1.6 mm

0 to 4 mm

0 to 8 mm

Differential distance

E1, F1 models: 10% max. of sensing distance

Sensing object

Ferrous metal (Sensitivity lowers with non-ferrous metals)

Standard sensing object 
(mild steel)

12 x 12 x 1 mm

18 x 18 x 1 mm

30 x 30 x 1 mm

Response frequency*1

*1. The response frequencies are average values measured on condition that the distance between each sensing object is twice as large as the size of the sensing

object and the sensing distance set is half of the maximum sensing distance.

E1, F1 models: 1.5 kHz
D1 models: 800 Hz

E1, F1 models: 600 Hz, 
D1 models: 500 Hz

E1, F1 models: 400 Hz, 
D1 models: 300 Hz

Power supply
(Operating voltage 
range)

E1, F1 models: 12 to 24 VDC, ripple (p-p) : 10% max., (10 to 30 VDC)
D1 models: 12 to 24 VDC, ripple (p-p) : 20% max., (10 to 36 VDC)

Current consumption

E1, F1 models: 17 mA max.

Leakage current

D1 models: 0.8 mA max.

Control 
output

Switching 
capacity

E1, F1 models: 200 mA max., D1 models: 5 to 100 mA DC

Residual 
voltage

E1, F1 models: 2 V max. (load current: 200 mA with cable length: 2 m)
D1 models: 4.0 V max. (under load current of 100 mA with cable length of 2 m)

Indicator lamp

E,D models: detection indicator (red)

Operating status 
(with sensing object 
approaching)

Normally open (NO)

Protective circuits

E1, F1 models: Protection for reverse polarity, load short circuit, surge voltage

Ambient temperature

Operating/Storage: -25°C to 70°C (with no icing or condensation)

Ambient humidity

Operating/Storage: 35% to 95%RH (with no condensation)

Temperature influence

10% max. of sensing distance at 23°C within temperature range of -25°C to 70°C

Voltage influence

E1, F1 models: ±2.5% max. of sensing distance within rated voltage range ±15%

Insulation resistance

50 M

W

 min. (at 500 VDC) between energized parts and case

Dielectric strength

E1, F1, D1 models: 1,000 VAC 50/60 Hz for 1 min between energized parts and case

Vibration resistance

Destruction: 10 to 55 Hz, 1.5 mm double amplitude for 2 hours each in X, Y, and Z directions

Shock resistance

Destruction: 500 m/s

2

 for 10 times 

each in X, Y, and Z directions

Destruction: 1,000 m/s

2

 for 10 times each in X, Y, and Z directions

Protective structure

IEC60529 IP67

Connection method

Pre-wired models (standard length: 2 m)

Weight (Packed state)

Approx. 70 g

Approx. 130 g

Approx. 170 g

Material

Case

Fluoro plastic

Sensing 
surface

Accessories

Instruction manual

Содержание E2FQ

Страница 1: ...Q X5D1 500 Hz M30 E2FQ X10F1 E2FQ X10E1 400 Hz E2FQ X10D1 300 Hz Shielded 2mm 5mm 10mm E2FQ X2 E2FQ X5 E2FQ X10 Side length of sensing object d mm Sensing distance X mm 0 5 10 15 20 25 2 4 2 2 2 1 8 1 6 1 4 1 2 1 0 8 0 6 0 4 0 2 Aluminum Stainless steel SUS304 Mild steel Brass d t 1mm X Side length of sensing object d mm Sensing distance X mm 0 5 10 15 20 25 30 35 40 50 7 6 5 4 3 2 1 Aluminum Stai...

Страница 2: ...nt 200 mA with cable length 2 m D1 models 4 0 V max under load current of 100 mA with cable length of 2 m Indicator lamp E D models detection indicator red Operating status with sensing object approaching Normally open NO Protective circuits E1 F1 models Protection for reverse polarity load short circuit surge voltage Ambient temperature Operating Storage 25 C to 70 C with no icing or condensation...

Страница 3: ... DC 2 wire E2FQ X D1 Yes No Operates Releases H L Load between black and blue leads Output voltage between black and blue leads Sensing object ON OFF Operation indicator Brown Black Output Blue 100W 4 7kW 2 2W Main circuit V 0V Load Yes No Operates Releases H L Load between black and blue leads Output voltage between black and blue leads Sensing object ON OFF Operation indicator Brown Black Output...

Страница 4: ... can be extended in an independent conduit for 200 m maximum E2FQ X5E1 E2FQ X5F1 29 dia 40 47 32 29 24 8 M18 x 1 Two Toothed washers Two clamping nut Indicator see note Note Oil resistant vibration resistant and fire retardant vinyl insulated round cord 6 dia x 2 cores standard length 2 m The cord can be extended in an independent conduit for 200 m maximum E2FQ X5D1 42 dia 36 57 50 41 38 8 M30 x 1...

Страница 5: ...suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this document Nuclear energy control systems combustion systems railroad sys tems aviation systems medical equipment amusement machines vehicles safety equipment and installations subject to separate in dustry or government regulations Systems mach...

Отзывы: