background image

3

DRT2-ID16/OD16

DRT2-ID16/OD16

For more information, contact an Omron representative at 1-800-55-OMRON

Operating Time Monitor Function

Errors in machine operation can be detected by measuring 
the time interval between output and input.

The Slave can perform high-speed measurement of the interval 
between the time an output is turned ON by a specified bit and the 
time an input is turned ON. It is possible to read this measurement 
result (between 2 and 65,535 ms) using the Configurator or explicit 
message communications. This feature contributes to preventive 
maintenance by allowing the detection of mechanical deteriora-
tion, such as air leaks in cylinders. A threshold value can also be 
set in the Slave so that a flag turns ON when the time becomes 
longer than a set time.

Contact Operation Counter Function

Provides notification of maintenance timing for I/O devices, 
such as switches and actuators.

This function provides notification of maintenance timing for input 
and output devices, such as switches and actuators.

Energized Time Monitor Function

Every six minutes the Slave records the total energized time of, for 
example, a motor. This record can be read using the Configurator 
or explicit message communications.

MS NS   NODE ADDRESS

DRT2-ID16

ET-OD16

Measurement 
time

Measurement 
time

Smart Slave

Output contact A 
(e.g., valve)

Output contact A 
(e.g., valve)

Input contact B 
(e.g., sensor)

Recorded in 

the Slave

Measurement 
time

Input contact B 
(e.g., sensor)

Note: This function can only be used when combinations of
          Basic Units and Expansion Units that have both inputs
          and outputs are used.

MS NS   NODE ADDRESS

DRT2-ID16

1             2             3  

Number 
of times

OFF to ON

Output device 
(e.g., relay)

Counts the number 
of OFF to ON 
operations

Smart Slave

Recorded in 

the Slave

MS NS   NODE ADDRESS

DRT2-ID16

Smart Slave

Total conduction
time

I/O power 
supply

Motor

Motor's 
conduction time

Total conduction
time

Recorded in 

the Slave

Note: The contact operation counter function and the unit conduction time monitor
          function cannot be used simultaneously.

Содержание DeviceNet DRT2-ID16

Страница 1: ...ounting keeps track of the ON OFF operations and total operating time so preventive maintenance can be scheduled based on service life estimates The operation counter and operating time monitor functi...

Страница 2: ...independently of control systems PLC Configurator Control I O DRT2 series Smart Slave Pneumatic valve Maintenance information Easy to view Display 2 3 Sensor Cylinder Control System Maintenance System...

Страница 3: ...nction provides notification of maintenance timing for input and output devices such as switches and actuators Energized Time Monitor Function Every six minutes the Slave records the total energized t...

Страница 4: ...nd model number for each contact e g sensors and valves comments can be set for each of the input and output contacts in the Slaves Confirmation and preparation of replacement parts when failures occu...

Страница 5: ...t Slaves that are removed from the network when correcting an error enabling more effective maintenance Improved Structural Flexibility Smallest in Its Class The width of the Basic Unit is 115 mm 77 o...

Страница 6: ...ening torque M3 power supply I O terminals 0 3 to 0 5 N m Item Specification Model number DRT2 ID16 DRT2 ID16 1 Internal I O common processing NPN PNP Number of I O points 16 inputs ON voltage 15 VDC...

Страница 7: ...NP Photocoupler Photocoupler Photocoupler Photocoupler 0 1 G V 24 VDC 0 1 G V 24 VDC Internal circuit Internal circuit Voltage step down Voltage step down DRT2 ID16 1 PNP DRT2 ID16 NPN V 10 1 11 3 12...

Страница 8: ...pansion outputs NPN XWT 0D08 8 expansion outputs PNP XWT OD08 1 16 expansion inputs NPN XWT ID16 16 expansion inputs PNP XWT ID16 1 16 expansion outputs NPN XWT OD16 16 expanison outputs PNP XWT OD16...

Отзывы: