Wiring

Do not connect the lead wires directly to the terminals. Connect the
lead wires through insulation tubes and M3.5 crimp terminals.
Tighten each terminal screw within the proper torque range.

The proper lead wire is AWG20 to AWG14 (0.5 to 2.5 mm

2

) in size.

Make sure that all crimp terminals are correctly connected and
located within the casing or cover as shown below.

Connector

Tighten the connector to a suitable torque. Excessive tightening
torque may damage the casing.

When using a 1/2-14NPT conduit, apply sealing tape between con-
nector and conduit opening so that the enclosure will confirm to IP67.
If using a Pg13.5 conduit, use an ABS-08 Pg13.5 connector or an
ABS-12 Pg13.5 connector (manufactured by Nippon Flex).

Use a connector (SC Series, sold separately) suitable for the outer
diameter of the cable.

When wiring a 3-conduit model, securely tighten the cap screw pro-
vided for unused conduit openings.

Maintenance and Repairs

The user must not maintain or repair equipment incorporating any
D4BS model. Contact the manufacturer of the equipment for any
maintenance or repairs required.

D dia.

dz dia.

dz dia.:  3.7
D dia.:  4.5
B: 7.0
L: 20.2
F: 7.7
I: 9.0 

(mm)

Casing 

Cover 

Terminal screw

Crimp terminal

Terminal screw

Casing 

Terminal screw

Cover 

Crimp terminal

Correct

Correct

Incorrect

Incorrect

Crimp 
terminal

Crimp terminal

Crimp terminal

F502-EN2-04.book  Seite 151  Dienstag, 26. Juli 2005  5:48 17

Содержание D4BS -

Страница 1: ...odel Number Legend Ordering Information List of Models Switches Prefered stock item Type Mounting direction Conduit size 1NC 1NO Slow action 2NC Slow action 1 conduit Front side mounting Pg13 5 D4BS 1...

Страница 2: ...e UL CSA UL508 CSA C22 2 No 14 A600 Type Model D4BS K1 D4BS K2 D4BS K3 Horizontal mounting Vertical mounting Adjustable mounting Horizontal Agency Standard File No T V Rheinland EN60947 5 1 UL UL508 E...

Страница 3: ...and ground and between each ter minal and non current carrying metal part Contact resistance 25 m max initial value Rated insulation voltage Ui 600 V EN60947 5 1 Conventional enclosed thermal current...

Страница 4: ...contacts from each other by using shearing force if any abnormality such as contact welding should occur in the contact area There is a difference in level between the NC and NO terminal which assures...

Страница 5: ...amping screws Six 5 3 dia mounting holes Four M3 5 x 10 cover clamping screws D4BS 1 S Pg13 5 D4BS 2 S G1 2 D4BS 4 S 1 2 14NPT D4BS 5 S 3 Pg13 5 D4BS 6 S 3 G1 2 D4BS 8 S 3 1 2 14NPT 30 0 2 19 61 N max...

Страница 6: ...Key insertion radius in horizontal direction R 1200 53 5 min 58 max Operation Key insertion radius in horizontal direction R 1000 D4BS 1 S D4BS K2 D4BS 2 S D4BS K2 D4BS 4 S D4BS K2 54 5 min 59 max Ope...

Страница 7: ...on Locations where the product may come into direct contact with pro cessing waste or dust Operation Key Be sure to use a special Operation Key only Do not operate the D4BS with anything other than th...

Страница 8: ...d Mounting Direction By removing the screws on the four corners of the head the head can be reset in any of four directions The head direction can be changed with or without the Operation Key inserted...

Страница 9: ...ing so that the enclosure will confirm to IP67 If using a Pg13 5 conduit use an ABS 08 Pg13 5 connector or an ABS 12 Pg13 5 connector manufactured by Nippon Flex Use a connector SC Series sold separat...

Страница 10: ...est of product improvement specifications are subject to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounc...

Отзывы: