64
Segment Program 2 (Block Model 157)
Section 6-7
8: Y1 Bar Display
A Level Meter object is used to display tag ITEM Y1 (ITEM 008: Program out-
put). The meter color is yellow, maximum value is 11500 (115%), and mini-
mum value is
−
1500 (
−
15%). The bar is set to display the zero point.
9: WAIT Button
When touched, 1 is set in the write address for tag ITEM S3 (ITEM 017).
When tag ITEM U10 (ITEM 019), Waiting, is 0, the button is yellow, and when
the value is 1, the button is displayed in red.
The button is built using a momentary ON/OFF Button with a Simple Rectan-
gle (Type 2). The write address for tag ITEM S3 (ITEM 017) is set as the write
address, and the read address for tag ITEM U10 (ITEM 019) is set as display
address 1. The label displays “WAIT” in the rough font.
10: ADV Button
When touched, 1 is set in the write address for tag ITEM S4 (ITEM 018) step
command. Tag ITEM S4 (ITEM 018) is displayed in yellow when the value is
0, and in red when the value is 1.
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address for tag ITEM S4 (ITEM 018) is set as the write
address, and the read address for tag ITEM S4 (ITEM 018) is set as display
address 1. The label displays “ADV” in the rough font.
11: START Button
When touched, 1 is set in the write address for tag ITEM S1 ITEM013, Run/
stop command. Tag ITEM S1 (ITEM 013) is referenced and the color is dis-
played according to the following table.
The button is built as a momentary ON/OFF Button using a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S1
(ITEM 013) is set as display address 1. The label displays “START” in the
rough font.
The following macro is set as a Touch OFF Timing macro, and when touched,
the fixed value 1 is written to the write address of tag ITEM S1 (ITEM 013).
$B32766=1;
WRITECMEM ([S1],$B32766,1) ;
12: STOP Button
When touched, 0 is set in the write address for tag ITEM S1 (ITEM 013), Run/
stop command. Tag ITEM S1 (ITEM 013) is referenced and the color is dis-
played according to the following table.
The button is built as a momentary ON/OFF Button with a Simple Rectangle
(Type 2). The write address is not set, and the read address for tag ITEM S1
(ITEM 013) is set as display address 1. The label displays “STOP” in the
rough font.
S1 (ITEM 013) value
Color
0
Yellow
1
Red
S1 (ITEM 013) value
Color
0
Red
1
Yellow
Содержание CXONE-ALD-V4 - 10-2010
Страница 2: ......
Страница 4: ...iv...
Страница 6: ...vi...
Страница 14: ...xiv...
Страница 22: ...6 Upgrades Made for Version 3 1 Section 1 6...
Страница 28: ...12 Uninstalling the Face Plate Auto Builder for NS Section 2 2...
Страница 29: ...13 SECTION 3 Basic Operation Flow 3 1 Basic Operation Flow 14...
Страница 40: ...24 Merging Projects Section 4 2...
Страница 142: ...126 Segment Program 3 Block Model 158 Section 6 19...
Страница 144: ...128 Revision History...