7
.
Serial Communications Connection Procedure
34
12
Check the received data in the
CIO Window shown on the right.
In the example on the right, the
stored data starting from
CIO5500 are in hexadecimal and
are described as follows:
・
2804: Command code
・
0000: End code
・
01: Address number of Inverter
・
03: Function code
・
04: Number of bytes to read
・
00, 00, 00, 62: Read data
*For details, refer to
9.2.2
Detailed Description of the
Function
.
13
On Digital Operator, check the
values of Total Power ON Time
Monitor that are already read
out.
Press the
Mode
Key to display
the parameter of Monitor Mode
''d''.
*If the output frequency is not
displayed in Data display, press
and hold the
Mode
Key for 3
seconds or more to display the
output frequency.
0.00
d001
14
Press the
Increment
Key or the
Decrement
Key to display d017.
d001
(
)
d017
15
Press the
Enter
Key to display
the total power ON time.
*For information on the display of
the total power ON time, refer to
7-1-16 Total Power ON Time
Monitor [d017]
of the
Multi-function Compact Inverter
MX2 Series Type V1 User’s
Manual
(Cat. No. I585).In the
example on the right, the total
power ON time shows 98, and it
accords with the read data
(00000062 in hexadecimal)
described in step 12.
Output frequency
Monitor Mode
Parameter display
Total Power ON Time Monitor