984
Block Programming Instructions
Section 3-32
Description
BPRG(096) executes the block program with the block number designated in
N, i.e., the one immediately after it and ending with BEND(801). All instruc-
tions between BPRG(096) and BEND(801) are executed with ON execution
conditions (i.e., unconditionally).
When the execution condition for BPRG(096) is OFF, the block program will
not be executed and no execution time will be required for the instruction in
the block program.
Execution of the block program can be stopped using BPPS(811) from within
another block program even if the execution condition for BPRG(096) is ON.
Flags
BPRG(096)
BEND(801)
Precautions
Each block program number can be used only once within the entire user pro-
gram.
Block programs cannot be nested.
Indirect DM/EM
addresses in binary
---
Indirect DM/EM
addresses in BCD
---
Constants
0 to 127 (decimal)
Data Registers
---
Index Registers
---
Indirect addressing
using Index Registers
---
Area
N
Block program
Executed when the execu-
tion condition is ON.
Name
Label
Operation
Error Flag
ER
ON if BPRG(096) is already being executed.
ON if N is not between 0 and 127.
ON if the same block program number is used more than
once.
OFF in all other cases.
Name
Label
Operation
Error Flag
ER
ON if a block program is not being executed.
OFF in all other cases.
Nesting NOT possible.
Содержание CJ1G-CPUxx
Страница 3: ...iv N o t i c e ...
Страница 5: ...vi ...
Страница 21: ...xxii Conformance to EC Directives 6 ...
Страница 35: ......
Страница 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Страница 1143: ...Authorized Distributor Cat No W340 E1 08 Note Specifications subject to change without notice Printed in Japan ...