background image

EN-9

„

Main Circuit Terminals

Main circuit terminal functions are summarized according to terminal symbols in 

Table 1

. Wire the

terminals correctly for the desired purposes.

Table 1   Main Circuit Terminal Functions (200 V Class and 400 V Class)

„

Control Circuit Terminals

Fig 5

 shows the control terminal arrangement. The functions of the control circuit terminals are

shown in 

Table 2

. Use the appropriate terminals for the correct purposes.

Fig 5  Control terminal arrangement

Table 2  Control Circuit Terminals with default settings

Purpose

Terminal Symbol

Model: CIMR-E7Z

††††

200 V Class

400 V Class

Main circuit power input

R/L1, S/L2, T/L3

20P4 to 2110

40P4 to 4300

R1/L11, S1/L21, T1/L31

2022 to 2110

4022 to 4300

Inverter outputs

U/T1, V/T2, W/T3

20P4 to 2110

40P4 to 4300

DC bus terminals

1, 

20P4 to 2110

40P4 to 4300

DC reactor connection

1, 2

20P4 to 2018

40P4 to 4018

Braking Unit connection

3, 

2022 to 2110

4022 to 4300

Ground

20P4 to 2110

40P4 to 4300

Type

No.

Signal Name

Function

Signal Level

Digital inp

u

t signals

S1

Forward run/stop command

Forward run when ON; stopped when 
OFF.

24 VDC, 8 mA
Photocoupler isolation

S2

Reverse run/stop command

Reverse run when ON; stopped when 
OFF.

S3

External fault input

*1

Fault when ON.

Functions are 
selected by 
setting H1-01 to 
H1-05.

S4

Fault reset

 

*1

Reset when ON

S5

Multi-step speed reference 1 

*1

(Master/auxiliary switch)

Auxiliary frequency ref-
erence when ON.

S6

Multi-step speed reference 2 

*1

Multi-step speed 2 
when ON.

S7

Jog frequency reference 

*1

Jog frequency when 
ON.

SC

Digital input common

SN

Digital Input Neutral

SP

Digital Input Power Supply

+24VDC power supply for digital inputs

24 VDC, 250 mA max. 

*2

Analog input signals

+V

15 V power output

15 V power supply for analog references

15 V (Max. curr.: 
20mA)

A1

Frequency reference

0 to +10 V/100%

0 to +10 V (20 k

Ω

)

A2

Auxiliary Frequency Refer-
ence

Auxiliary analog fre-
quency reference;
4 to 20 mA (250

Ω)

Function is 
selected by 
setting H3-09.

4 to 20 mA (250

Ω

)

0 V to +10 V (20k

Ω

)

0 to 20 mA (250

Ω

)

-V

-15 V power output

-15 V power supply for analog references

AC

Analog reference common

E(G)

Shield wire, optional ground 
line connection point

Содержание CIMR-E7Z -

Страница 1: ...own Model CIMR E7Z 200V Class Single phase 0 4 to 110 kW 400V Class 3 phase 0 4 to 300 kW Quick START GUIDE Manual No I64E EN 01 VARISPEED E7 Quick Start Guide Manual No I64E EN 01 English Deutsch Esp...

Страница 2: ...Wiring Main Circuit Inputs EN 11 Keypad Operation EN 13 Digital Operator Display optional EN 13 Power Up and Basic Parameter Setup EN 15 Start Up Procedure EN 15 Before Power Up EN 16 Display after Po...

Страница 3: ...eneral LC RC interference suppression filters capacitors or overvoltage protection devices to the inverter input or output To avoid unnecessary overcurrent faults etc being displayed the signaling con...

Страница 4: ...ther unauthorized persons must not be allowed access to these inverters Keep these Safety Precautions and Instructions for Use readily accessible and supply them to all persons with any form of access...

Страница 5: ...y inverters design and install electrical switch gear It also describes the measures necessary to comply with the EMC Directive The manual s installation and wiring instructions must therefore be foll...

Страница 6: ...s so as to maximize the area of the end of the lead in contact with the ground terminal e g metal plate Shielded Cable Use a cable with braided shield Ground the maximum possible area of the shield It...

Страница 7: ...d from floating dust When installing or operating the Inverter always take special care so that metal powder oil water or other foreign matter does enter the Inverter Do not install the Inverter on co...

Страница 8: ...required horizontally and vertically for IP00 IP20 and NEMA 1 Inverters 2 Always remove the top protection cover after installing an Inverter with an output of 18 5 kW or less in a panel Always provid...

Страница 9: ...0 to 10 V 3 2 k 2 1 V 2 k Reverse Run Stop External fault Fault reset Multi step speed setting 1 Multi step speed setting 2 Jog frequency selection Multi function digital inputs Factory settings Anal...

Страница 10: ...gnal Name Function Signal Level Digital input signals S1 Forward run stop command Forward run when ON stopped when OFF 24 VDC 8 mA Photocoupler isolation S2 Reverse run stop command Reverse run when O...

Страница 11: ...tions output Differential input PHC isolation S IG Signal common 1 The default settings are given for terminals S3 to S7 For a 3 wire sequence the default settings are a 3 wire sequence for S5 multi s...

Страница 12: ...on PNP by using the jumper CN5 An external power supply is also supported providing more freedom in signal input methods Table 3 Sinking Sourcing Mode and Input Signals Internal Power Source Sinking M...

Страница 13: ...300A 9000 2055 215 240 350 4000 55000 A50P350 4 500V 350A 12000 2075 283 240 450 7100 64000 A50P450 4 500V 450A 20000 2090 346 240 550 11000 64000 A50P600 4 500V 600A 36000 2110 415 240 600 13000 830...

Страница 14: ...contactor MC between the Inverter and motor is not turned ON or OFF during inverter operation If the MC is turned ON during the Inverter is operation a large inrush current will be created and the in...

Страница 15: ...ey Selects user parameter numbers and decrements parameter set tings Used to move to the previous item or data DATA ENTER Key Enters menus and parameters and validates parameter settings RUN Key Start...

Страница 16: ...ower ON Confirm Status Basic settings Quick Programming Mode Set E1 03 V f default 400V 50Hz Motor cable over 50 m or heavy load possibly causing motor to stall or overload Non rotating autotuning for...

Страница 17: ...Autotuning can be used to improve the performance when very long motor cables are used or when motor and inverter have different power ratings To perform autotuning set T1 02 Motor rated power and T1...

Страница 18: ...lculation 1 Enabled speed calculation 2 Disabled current detection 3 Enabled current detection b3 14 Bi directional speed search selection Disables or enables the bi directional capabilities of the sp...

Страница 19: ...or protec tion selection 0 Disabled 1 General purpose motor protection fan cooled motor 2 Inverter motor protection externally cooled motor 3 Vector motor protection When the Inverter power supply is...

Страница 20: ...0 Input terminal status Shows input ON OFF status Param eter Num ber Name Description 1 FWD command S1 is ON 1 REV command S2 is ON 1 Multi input 1 S3 is ON 1 Multi input 2 S4 is ON 1 Multi input 3 S5...

Страница 21: ...inal is not used 14 Fault reset Reset when turned ON 19 PI control disable 20 to 2F External fault Input mode NO contact NC contact Detection mode Normal during operation Digital Output Function Selec...

Страница 22: ...motor Check external sequence logic so that only one input is activated at a time External fault input from Communications Option Card Check for an external fault condition Verify the parameters Verif...

Страница 23: ...rrent matches the motor rated current only in stop condi tio The DC bus voltage has exceeded the overvolt age detection level Default detection levels are 200 V class 410 VDC 400 V class 820 VDC Incre...

Страница 24: ...parameter b1 02 are set to 3 option board but no option board is installed Verify that the board is installed Remove the power supply and re install the option board again Recheck the setting of b1 01...

Отзывы: